Application - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 14
Control
14.4.3.1
14.4.3.2
14.4.3.3
352

Application

The interlocking for bus-coupler bay (ABC_BC) function is used for a bus-coupler
bay connected to a double busbar arrangement according to figure 134. The
function can also be used for a single busbar arrangement with transfer busbar or
double busbar arrangement without transfer busbar.
QB1
QB2
QC1
QA1
IEC04000514 V1 EN-US
Figure 134:
Switchyard layout ABC_BC
Configuration
The signals from the other bays connected to the bus-coupler module ABC_BC are
described below.
Signals from all feeders
To derive the signals:
Signal
BBTR_OP
No busbar transfer is in progress concerning this bus-coupler.
VP_BBTR
The switch status is valid for all apparatuses involved in the busbar transfer.
EXDU_12
No transmission error from any bay connected to the WA1/WA2 busbars.
These signals from each line bay (ABC_LINE), each transformer bay
(AB_TRAFO), and bus-coupler bay (ABC_BC), except the own bus-coupler bay
are needed:
Signal
QQB12OPTR
QB1 or QB2 or both are open.
VPQB12TR
The switch status of QB1 and QB2 are valid.
EXDU_12
No transmission error from the bay that contains the above information.
WA1 (A)
WA2 (B)
WA7 (C)
QB20
QB7
QC2
en04000514.vsd
1MRK 511 401-UEN A
M13555-3 v8
M13553-138 v4
M13553-6 v4
Bay control REC670 2.2 IEC
Application manual