Examples On How To Connect, Configure And Set Ct Inputs For Most Commonly Used Ct Connections - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 4
Analog inputs
4.2.2.4
66
The main CT ratios must also be set. This is done by setting the two parameters
CTsec and CTprim for each current channel. For a 1000/1 A CT, the following
settings shall be used:
CTprim = 1000 (value in A)
CTsec =1 (value in A).
Examples on how to connect, configure and set CT inputs for most
commonly used CT connections
Figure
12
defines the marking of current transformer terminals commonly used
around the world:
In the SMAI function block, you have to set if the SMAI block is
measuring current or voltage. This is done with the parameter:
AnalogInputType: Current/Voltage. The ConnectionType: phase -
phase/phase-earth and GlobalBaseSel.
I
Sec
x
a)
IEC06000641 V1 EN-US
Figure 12:
Commonly used markings of CT terminals
Where:
a)
is symbol and terminal marking used in this document. Terminals marked with a square
indicates the primary and secondary winding terminals with the same (that is, positive)
polarity
b) and
are equivalent symbols and terminal marking used by IEC (ANSI) standard for CTs. Note that
c)
for these two cases the CT polarity marking is correct!
It shall be noted that depending on national standard and utility practices, the rated
secondary current of a CT has typically one of the following values:
1A
5A
P1
(H1)
S1 (X1)
S2 (X2)
x
P2
(H2)
b)
1MRK 511 401-UEN A
SEMOD55055-296 v7
P2
(H2)
S2 (X2)
S1 (X1)
P1
(H1)
c)
en06000641.vsd
Bay control REC670 2.2 IEC
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents