5.3 Installing AC Output Power Cables

Connect the SUN2000 to the AC power distribution frame (PDF) or power grid using AC
output power cables.
Prerequisites
An independent three-phase circuit breaker must be installed on the AC side of each
SUN2000 to ensure that the SUN2000s can be safely disconnected from the power grid. See
10 Technical Specifications
Context
Table 5-1 AC output cable specifications
Inverter Model
SUN2000-33KT
L
SUN2000-40KT
L
Issue 03 (2015-12-01)
Do not install a single circuit breaker for several SUN2000s.
Do not connect loads between the SUN2000 and circuit breaker.
Outdoor copper-core cables are recommended.
Cable Type
4-core
outdoor cable
(L1, L2, L3,
and N)
3-core
outdoor cable
(L1, L2, and
L3)
The customer needs to prepare OT terminals. The SUN2000-33KTL requires M6 OT
terminals and a cable with the maximum cross-sectional area of 25 mm
connected. The SUN2000-40KTL requires M8 OT terminals and a cable with the
maximum cross-sectional area of 35 mm
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
to select the circuit breaker of the appropriate specifications.
Cross-sectional Area
(mm
)
2
Range
16–25 (or
6–3 AWG)
16–35 (or
6–2 AWG)
2
can be connected.
5 Electrical Connections
Table 5-1
describes the specifications.
Cable Outer
Diameter (mm)
Recomme
Range
nded
Value
16 (or 6
24–32
AWG)
Recomm
ended
Value
28
2
can be
47