Huawei SUN2000-33KTL User Manual page 58

Hide thumbs Also See for SUN2000-33KTL:
Table of Contents

Advertisement

SUN2000-(33KTL, 40KTL)
User Manual
Table 5-2 DC terminal selection requirements
Number of Inputs
1
2
3
4
5
6
Table 5-3 Recommended DC input cable specifications
Cable Type
Common PV cables in
the industry (model:
PV1-F)
Highly rigid cables, such as armored cables, are not recommended because bending may
cause poor contact.
Issue 03 (2015-12-01)
Figure 5-11 DC terminals
SUN2000-33KTL/40KTL
Connected to any one route
Connected to routes 1 and 3
Connected to routes 1, 3, and 5
Connected to routes 1, 2, 3, and 5
Connected to routes 1, 2, 3, 4, and 5
Connected to routes 1, 2, 3, 4, 5, and 6
DC input cable specifications
Table 5-3
lists the recommended DC input cable specifications.
Cross-sectional Area (mm
Range
4.0–6.0 (or 12–10
AWG)
Positive and negative connectors
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connections
)
Cable Outer
2
Diameter (mm)
Recommended
Value
4.0 (or 12 AWG)
4.5–7.8