Huawei SUN2000-33KTL User Manual page 65

Hide thumbs Also See for SUN2000-33KTL:
Table of Contents

Advertisement

SUN2000-(33KTL, 40KTL)
User Manual
Select either connection mode during installation. Connecting to a terminal block is recommended.
When routing communications cables, ensure that communications cables are separated from
power cables and away from interfering source to prevent communication from being
affected.
Table 5-4
Table 5-4 RS485 terminal block definitions
No.
5
7
Issue 03 (2015-12-01)
Terminal block connection
The DJYP2VP2-22 2x2x1 network cable or a communications cable with a cross
sectional area of 1 mm
RJ45 network port connection
You are advised to use a CAT 5E outdoor shielded network cable with a diameter
less than 9 mm and internal resistance no greater than 1.5 ohms/10 m.
RS485 terminal block definitions
Figure 5-22 Terminal block
defines the RS485 terminal block.
Function
RS485A (IN)
RS485B (IN)
RJ45 connector pin definitions
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2
and external diameter of 14–18 mm is recommended.
No.
6
8
5 Electrical Connections
Function
RS485A (OUT)
RS485B (OUT)