CHAPTER 4: ACTUAL VALUES

A2 Metering

Current

350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
The relay measures all RMS currents and voltages, frequency, and all auxiliary analog
inputs. Other values like neutral current, symmetrical components, power factor, power
(real, reactive, apparent), are derived. All quantities are recalculated every power system
cycle and perform protection and monitoring functions. Displayed metered quantities are
updated approximately three (3) times a second for readability. All phasors and
symmetrical components are referenced to the A-N voltage phasor for wye-connected
VTs; to the A-B voltage phasor for delta connected VTs; or to the phase A current phasor
when no voltage signals are present.
By scrolling the Up/Down keys the relay shows one-by-one, all metered values as follows:
Path:
ACTUAL VALUES > A2 METERING > CURRENT
PH A CURRENT
o
0.0 A 0
lag
Range: 0.0 to 30000 A, 0 to 359
PH B CURRENT
o
0.0 A 0
lag
Range: 0.0 to 30000 A, 0 to 359
PH C CURRENT
o
0.0 A 0
lag
Range: 0.0 to 30000 A, 0 to 359
NTRL CURRENT
o
0.0 A 0
lag
Range: 0.0 to 30000 A, 0 to 359
GND CURRENT
o
0.0 A 0
lag
Range: 0.0 to 30000 A, 0 to 359
SENS GND CURRENT
o
0.00 A 0
lag
Range: 0.00 to 15.00 A, 0 to 359
POS SEQ CURRENT
o
0.0 A 0
lag
Range: 0.0 to 30000 A, 0 to 359
NEG SEQ CURRENT
o
0.0 A 0
lag
Range: 0.0 to 30000 A, 0 to 359
ZERO SEQ CURRENT
o
0.0 A 0
lag
Range: 0.0 to 30000 A, 0 to 359
PH A CURRENT 2nd HRMC
0.0 %
Range: 0.0 to 100.0%
PH B CURRENT 2nd HRMC
0.0 %
Range: 0.0 to 100.0%
o
lag
o
lag
o
lag
o
lag
o
lag
o
lag
o
lag
o
lag
o
lag
A2 METERING