GE 350-A9 Instruction Manual page 162

Feeder protection system feeder protection and control
Hide thumbs Also See for 350-A9:
Table of Contents

Advertisement

S3 PROTECTION
6–32
multiple of the source CT. For example, if 100: 5 CTs are used and a pickup of 90 amps
is required for the time overcurrent element, enter "0.9 x CT".
<Element_Name> CURVE: Select the desired curve shape. If none of the standard
curve shapes is appropriate, a custom FlexCurve™ can be created by entering the trip
times at 80 different current values; see S2 SYSTEM SETUP > FLEXCURVE A. Curve
formulas are given for use with computer based coordination programs. Calculated
trip time values are only valid for I / Ipu > 1. Select the appropriate curve shape and
multiplier, thus matching the appropriate curve with the protection requirements. The
available curves are shown in the table below.
ANSI
GE TYPE IAC
Extremely Inverse
Extremely Inverse
Very Inverse
Very Inverse
Normally Inverse
Inverse
Moderately Inverse
Short Inverse
<Element_Name> MULTIPLIER: A multiplier setpoint allows shifting of the selected
base curve in the vertical time direction. Unlike the electromechanical time dial
equivalent, trip times are directly proportional to the value of the time multiplier
setpoint. For example, all trip times for a multiplier of 10 are 10 times the multiplier 1
or base curve values.
When Timed Over-Current is programmed with Definite time, the operating time is
obtained after multiplication of the selected Multiplier (TDM) by a 0.1 s base line. For
example, selection of TDM = 5 would lead to a 0.5 s operating time.
<Element_Name> RESET: Time overcurrent tripping time calculations are made with
an internal 'energy capacity' memory variable. When this variable indicates that the
energy capacity has reached 100%, a time overcurrent trip is generated. If less than
100% is accumulated in this variable and the current falls below the dropout threshold
of 97 to 99% of the pickup value, the variable must be reduced. Two methods of this
resetting operation are available, Instantaneous and Linear. The Instantaneous
selection is intended for applications with other relays, such as most static units,
which set the energy capacity directly to zero when the current falls below the reset
threshold. The Linear selection can be used where the relay must coordinate with
electromechanical units. With this setpoint, the energy capacity variable is
decremented according to the following equation.
where: T
= reset time in seconds; E = energy capacity reached (per unit); M = curve
RESET
multiplier; CR = characteristic constant (5 for ANSI, IAC, Definite Time, and FlexCurves™; 8
for IEC)
ANSI Curves
The ANSI time overcurrent curve shapes conform to industry standards and the ANSI
C37.90 curve classifications for extremely, very, normally, and moderately inverse. The
ANSI curves are derived from the following formula:
where:T = trip time (seconds); M = multiplier value; I = input current; I
setpoint; A, B, C, D, E = constants
IEC
Curve A (BS142)
Curve B (BS142)
Curve C (BS142)
IEC Short Inverse
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: SETPOINTS
OTHER
Definite Time
TM
Flexcurve A
TM
Flexcurve B
User Curve
= pickup current
pu

Advertisement

Table of Contents
loading

Table of Contents