CHAPTER 6: SETPOINTS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 6-3: Menu for handling password security using keypad
S1 PASSWORD SECURITY
LOC SETPOINTS PSWD
LOC CONTROLS PSWD
PSWD FOR RESET KEY
The following steps describe how to change the Local Setpoints Password from the
keypad. Similar steps are followed to change the Local Control Password.
ENTER OLD PASSWORD
The user is prompted to enter the current Local Setpoints Password. User the value up/
down keys to select characters, and use the message left/right keys to move the cursor.
Press the Enter key when done. An INVALID PASSWORD message will appear if a wrong
password is entered, security is disabled, the password has not been originally set, or the
local user does not have the rights to change the password. In addition, the user will be
automatically logged out of security from the keypad. If the correct password was
entered, the user is now logged in to the Setpoints Level from the keypad, and will be
prompted to enter a new password.
ENTER NEW PASSWORD
The user is prompted to enter a new Local Setpoints Password. A valid password is
alphanumeric, and is 3 to 10 characters in length. An INVALID PASSWORD message will
appear if the new password does not meet the password requirements. If a valid password
was entered, the user will be prompted to re-enter the new password.
CONFIRM PASSWORD
The user is prompted to re-enter the new Local Setpoints Password. If the passwords do
not match, an ENTRY MISMATCH message will appear, the password will remain
unchanged, and the user will be returned to the Enter New Password page. If the
passwords match, a PASSWORD CHANGED message will appear indicating the Local
Setpoints Password has successfully been updated.
PASSWORD FOR RESET KEY
Range: Disabled, Enabled
Default: Disabled
If set to Enabled, a PASSWORD is required to reset Trip/Alarm LEDs and events when
pressing the Reset key. If set to Disabled, no password will be required.
When password security is enabled, the PSWD FOR RESET KEY is available, and set to
Disabled by default. Changing the value of "PSWD FOR RESET KEY" requires the Master
Password. If the Master Password has already been provided by the current user, further
password confirmation is not required for this setpoint (the 5 minutes of inactivity rule
does not apply).
S1 LOC SETPOINTS PSWD
ENTER OLD PASSWORD
ENTER NEW PASSWORD
CONFIRM NEW PASSWORD
S1 LOC CONTROLS PSWD
ENTER OLD PASSWORD
ENTER NEW PASSWORD
CONFIRM NEW PASSWORD
898772A2.cdr
S1 RELAY SETUP
6–11