Diagnostics And Troubleshooting - Wieland samos PRO COMPACT Manual

Hide thumbs Also See for samos PRO COMPACT:
Table of Contents

Advertisement

7.5

Diagnostics and troubleshooting

1031289099
Information on the diagnosis of the samosPRO system can be found in the software manual,
Section "List of all error messages".
Table 32: Troubleshooting on the SP-COP2-ENI module
Error
Key:
LED off /
The SP-COP2-ENI module
does not provide any data.
LED
PWR/EC
LED LINK
LED /ACT
MS LED
The SP-COP2-ENI module
does not provide any data.
LED
PWR/EC
LED LINK
LED /ACT
MS LED
The SP-COP2-ENI module
does not provide any data.
LED PWR
LED LINK
LED /ACT
MS LED
The SP-COP2-ENI module
does not provide any data.
LED
PWR/EC
LED LINK
LED /ACT
MS LED
Wieland Electric GmbH | BA000970 | 11/2016 (Rev. F)
Possible cause
LED flashes /
• The SP-COP2-ENI has
been configured for data
transmission to the PLC,
Green
but no Ethernet commu-
nication has been estab-
lished or the communica-
Green
tion is faulty.
• Duplicate IP address de-
Yellow
tected. Another network
Green
device has the same IP
address.
• Incorrectly formatted
PROFINET device name
• Configuration required.
• The configuration has not
yet been fully transmitted.
Green
• The module version does
not support any PROFI-
Green
NET IO.
Yellow
/
Red/gr
een
• The samosPRO system is
in the stop state.
Green
Green
Yellow
Green (1 Hz)
• The IP address for the SP-
COP2-ENI module is as-
signed by a DHCP server.
Green
Following a restart of the
SP-COP2-ENI module or
the DHCP server, another
Green
address was allocated to
the SP-COP2-ENI module,
Yellow
which is unknown to the
PLC.
Green
PROFINET IO-Gateway
Possible remedy
LED lights up
• PROFINET IO must be acti-
vated in the project file. At
least one Ethernet link must
be established. Check the
Ethernet wiring, check the
Ethernet settings in the PLC
and in samosPLAN5+.
• Correct the IP address and
switch the system off and on
again.
• Compare the device name
between the PROFINET mas-
ter and the SP-COP2-ENI
module.
• Configure the SP-COP2-ENI
module with a project file in
which PROFINET IO is acti-
vated and transfer the confi-
guration to SP-COP2-ENI
module.
• Use an SP-COP2-ENI device
starting with module version
B-xx.
• Start the controller module
(switch to Run mode).
• Either assign the SP-COP2-
ENI module a permanent IP
address or reserve a perma-
nent IP address for the SP-
COP2-ENI module in the
DHCP server (manual as-
signment using the MAC
address of the SP-COP2-ENI
module).
73