Module
no.
02
Wieland Electric GmbH | BA000970 | 11/2016 (Rev. F)
Diagnostic bit
Emergency
(M2 ... M5)
cause
00
Secure I/O
modules
01
02
03
04
05
06
07
08
09
10
11
12 to 15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
CANopen gateway
Emergency message
Reserved
Internal error: Internal tests failed
Reserved
Reserved
Configuration is incompatible or invalid
Output power supply not in permitted range
Reserved
Reserved
Two-channel evaluation of input 1-2: error de-
tected
Two-channel evaluation of input 3-4: error de-
tected
Two-channel evaluation of input 5-6: error de-
tected
Two-channel evaluation of input 7-8: error de-
tected
Reserved
Error of the external test signal at input 1.
Check whether there is a short-circuit to High
or a cabling error
Error of the external test signal at input 2.
Check whether there is a short-circuit to High
or a cabling error
Error of the external test signal at input 3.
Check whether there is a short-circuit to High
or a cabling error
Error of the external test signal at input 4.
Check whether there is a short-circuit to High
or a cabling error
Error of the external test signal at input 5.
Check whether there is a short-circuit to High
or a cabling error
Error of the external test signal at input 6.
Check whether there is a short-circuit to High
or a cabling error
Error of the external test signal at input 7.
Check whether there is a short-circuit to High
or a cabling error
Error of the external test signal at input 8.
Check whether there is a short-circuit to High
or a cabling error
Error: Short-circuit after high at output 1
Error: Short-circuit after low at output 1
Error: Short-circuit after high at output 2
Error: Short-circuit after low at output 2
Error: Short-circuit after high at output 3
Error: Short-circuit after low at output 3
Error: Short-circuit after high at output 4
141