Assigning device names via samosPLAN5+
Launch samosPLAN5+ and connect to the controller module SP-COP2-ENI.
Press the Stop button in the Hardware view to stop the application.
Click on the Hardware view in the blue area of the main window to open the right side of
the controller configuration.
Edit the connection name and click the Send button.
Illustration 14: Configuration dialog for the IP data and the device name
NOTICE
• The format of the device name must correspond to the specification of the PROFINET
standard.
• Ensure that the address for the default gateway matches the address set by the PLC for
the gateway. If no router is used, then Siemens Step 7 uses the same IP address for the
default gateway as for the SP-COP2-ENI module.
• If a project file with an active PROFINET IO is provided on the SP-COP2-ENI module, then
only one device in samosPLAN5+ can be found by USB. If you would like to use the
Ethernet to connect with the SP-COP2-ENI module then select Edit in the Connect dia-
log, where you then set the IP address of the SP-COP2-ENI module.
Use samosPLAN5+ to set the IP address
The IP address is typically assigned by the PROFINET IO controller (e.g. PLC). The SP-COP2-
ENI module, however, also allows the configuration of the entire samosPRO system via Ether-
net TCP/IP. It can be necessary in this case to already assign an IP address to the SP-COP2-ENI
before the PROFINET IO network is set up. This can also be done in the configuration dialog
shown above.
Wieland Electric GmbH | BA000970 | 11/2016 (Rev. F)
PROFINET IO-Gateway