Assigning device names via samosPLAN5+
 Launch samosPLAN5+ and connect to the controller module SP-COP2-ENI.
 Press the Stop button in the Hardware view to stop the application.
 Click on the Hardware view in the blue area of the main window to open the right side of
the controller configuration.
 Edit the connection name and click the Send button.
Illustration 14: Configuration dialog for the IP data and the device name
NOTICE
• The format of the device name must correspond to the specification of the PROFINET
standard.
• Ensure that the address for the default gateway matches the address set by the PLC for
the gateway. If no router is used, then Siemens Step 7 uses the same IP address for the
default gateway as for the SP-COP2-ENI module.
• If a project file with an active PROFINET IO is provided on the SP-COP2-ENI module, then
only one device in samosPLAN5+ can be found by USB. If you would like to use the
Ethernet to connect with the SP-COP2-ENI module then select Edit in the Connect dia-
log, where you then set the IP address of the SP-COP2-ENI module.
Use samosPLAN5+ to set the IP address
The IP address is typically assigned by the PROFINET IO controller (e.g. PLC). The SP-COP2-
ENI module, however, also allows the configuration of the entire samosPRO system via Ether-
net TCP/IP. It can be necessary in this case to already assign an IP address to the SP-COP2-ENI
before the PROFINET IO network is set up. This can also be done in the configuration dialog
shown above.