SDO 1003: Error list (error history)
SDO 1003 is an array that contains the last 10 error codes that the gateway has reported with
the aid of
emergency messages. Array index 0 contains the number of error codes recorded in SDO
1003.
A new error is recorded in index 1, while older errors will in this case be renumbered (incre-
mented by 1). The array index can be overwritten with a 0 from the outside, thus completely
deleting the array.
NOTICE
• Not all errors reported with the aid of emergency messages are recorded in SDO 1003,
only the errors listed here:
Error and state information for the modules [ch. 3.3.5, p. 23]
Messages [ch. 10.6, p. 140]
• The entries in SDO 1003 are in UDINT format and normally divided into 16 bits of error
code and 16 bits of additional information. In the event of an emergency, the module sta-
te diagnosis (4 bytes) will be entered here.
SDO 1005: COB ID SYNC
SDO 1005 contains the COB-ID of the sync object. This value has been preset to 80h, but can
be changed.
NOTICE
When you change the COB-ID of the sync object, please ensure that the new ID has not al-
ready been allocated to another communication object.
SDO 1008: Device name
SD0 1008 contains a device name (VISIBLE STRING).
NOTICE
This SDO cannot be read with a simple "SDO upload expedited". The "Upload SDO segment
protocol" command (client command code ccs = 3) must be used instead, as described in the
CANopen specifications DS 301.
SDO 1009: Hardware version
SDO 1009 contains the current hardware version of the device (VISIBLE STRING).
NOTICE
This SDO cannot be read with a simple "SDO upload expedited". The "Upload SDO segment
protocol" command (client command code ccs = 3) must be used instead, as described in the
CANopen specifications DS 301.
SDO 100A: Software version
SDO 100A contains the current software version of the device (VISIBLE STRING).
NOTICE
This SDO cannot be read with a simple "SDO upload expedited". The "Upload SDO segment
protocol" command (client command code ccs = 3) must be used instead, as described in the
CANopen specifications DS 301.