Allen-Bradley PowerFlex 525 User Manual page 39

Devicenet adapter catalog number: 25-comm-d
Hide thumbs Also See for PowerFlex 525:
Table of Contents

Advertisement

www.aotewell.com
As the selected DeviceNet path is browsed, RSNetWorx for DeviceNet
software creates a graph view window that shows a graphical
representation of the devices on the network.
If the icon for the drive (for this example, PowerFlex 525) on the network
appears as Unrecognized Device, use RSNetWorx for DeviceNet software
to create the PowerFlex 520-series drive EDS file. See
from Online Device on the Network on page 39
File from the Internet Web Site on page 40
create the EDS file.
Create the EDS File from Online Device on the Network
1. Right-click the Unrecognized Device icon and select Register Device in
the menu. The EDS Wizard appears.
2. Click Next to start creating the EDS file.
3. Select Create an EDS file.
4. Click Next.
If the EDS file is already downloaded and resides on your computer, select
"Register an EDS file" and click Next. Then follow the screen prompts and
disregard the remaining steps (5...13) in this procedure.
5. Enter a description (if desired).
Rockwell Automation Publication 520COM-UM002A-EN-E - April 2013
sales@aotewell.com
Industry Automation
Configuring the I/O
Chapter 4
Create the EDS File
or
Download the EDS
for instructions on how to
+86-755-8660-6182
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents