Allen-Bradley ControlNet 1786-RPA/B Installation Instructions Manual

Allen-Bradley ControlNet 1786-RPA/B Installation Instructions Manual

Modular repeater adapter

Advertisement

Installation Instructions
ControlNet Modular Repeater Adapter
Catalog Number 1786-RPA/B
Topic
About the Repeater Adapter Module
The 1786-RPA/B ControlNet repeater adapter module, which has a 24V DC,
removable power supply, can be used with 1786 repeater modules to build a
ControlNet network repeater. A repeater is used to extend the length of a
network, create a star, ring, or point-to-point topology, or perform network
media conversion from copper to fiber, and vice versa. A maximum of 20
repeater adapter can be placed in a series.
Page
2
3
4
5
6
8
13
16
19
23

Advertisement

Table of Contents
loading

Summary of Contents for Allen-Bradley ControlNet 1786-RPA/B

  • Page 1: Table Of Contents

    Installation Instructions ControlNet Modular Repeater Adapter Catalog Number 1786-RPA/B Topic Page Important User Information Environment and Enclosure North American Hazardous Location Approval European Hazardous Location Approval Features and Components of the ControlNet Repeater Adapter Mount the Repeater Adapter Module Wire the Repeater Adapter Module Status Indicators Specifications Additional Resources...
  • Page 2: Important User Information

    2 ControlNet Modular Repeater Adapter Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
  • Page 3: Environment And Enclosure

    ControlNet Modular Repeater Adapter 3 Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
  • Page 4: North American Hazardous Location Approval

    4 ControlNet Modular Repeater Adapter North American Hazardous Location Approval The following information applies Informations sur l’utilisation de cet when operating this equipment in équipement en environnements hazardous locations. dangereux. Products marked "CL I, DIV 2, GP A, B, C, D" are Les produits marqués "CL I, DIV 2, GP A, B, C, D"...
  • Page 5: European Hazardous Location Approval

    ControlNet Modular Repeater Adapter 5 European Hazardous Location Approval European Zone 2 Certification (The following applies when the product bears the Ex Marking.) This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
  • Page 6: Features And Components Of The Controlnet Repeater Adapter

    6 ControlNet Modular Repeater Adapter Prevent Electrostatic Discharge ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. •...
  • Page 7 ControlNet Modular Repeater Adapter 7 The repeater adapter also provides the following: • Digital re-timing of ControlNet network data • Power to repeater modules • One coax channel • Status indicators The repeater adapter ships with the following items: • One removable terminal block (power connector) attached to the repeater adapter.
  • Page 8: Mount The Repeater Adapter Module

    8 ControlNet Modular Repeater Adapter Mount the Repeater Adapter Module This section explains how to mount the 1786-RPA/B repeater adapter module. Horizontal mounting is preferred. Vertical mounting is allowed. We recommend that the 1786-RPA/B module be mounted at the top if vertical mounting is chosen. ATTENTION: This product is grounded through the DIN rail to chassis ground.
  • Page 9 ControlNet Modular Repeater Adapter 9 Do these steps to mount the 1786-RPA/B module. 1. Position the repeater adapter module on the 35 x 7.5 mm (1.4 x 0.3 in.) DIN rail (Allen-Bradley part number 199-DR1) at a 30 angle. 31454A-M 2.
  • Page 10 10 ControlNet Modular Repeater Adapter If the repeater adapter module does not snap into position, use a screwdriver or similar device to move the locking tab down while pressing the repeater adapter flush onto the DIN rail. 31454C-M 4. Release the locking tab to lock the adapter in place. If necessary, push up on the locking tab to lock.
  • Page 11 ControlNet Modular Repeater Adapter 11 WARNING: Removal and insertion under power (RIUP) is not supported. This module must be powered down while connecting and disconnecting it from any interconnected modules. If you insert or remove the module while backplane power is on, an electrical arc can occur.
  • Page 12 12 ControlNet Modular Repeater Adapter 7. Repeat steps through for each of the two DIN rail locks. For proper operation when using a 1786-RPFRXL/B module with a IMPORTANT 1786-RPCD module attached to the same 1786-RPA/B repeater module, you must install any 1786-RPCD module to the left side of any 1786-RPFRL or 1786-RPFRXL/B repeater module.
  • Page 13: Wire The Repeater Adapter Module

    ControlNet Modular Repeater Adapter 13 Wire the Repeater Adapter Module This section describes how to wire your module. WARNING: An electrical arc can occur under these circumstances: - when you connect or disconnect the removable terminal block (RTB) with field side power applied - if you connect or disconnect the communications cable with power applied to this module or any device on the network This could cause an explosion in hazardous location installations.
  • Page 14 14 ControlNet Modular Repeater Adapter + and V terminals 31456-M Tighten the screws to 0.6…0.8 N•m (5…7 in•lb). 3. Attach the V - wire to one of the V - terminals on the RTB. Tighten the screws to 0.6…0.8 N•m (5…7 in•lb). The unused V + and V - terminals can be used to supply power...
  • Page 15 ControlNet Modular Repeater Adapter 15 5. Connect the repeater adapter module to the ControlNet network by connecting the drop line of the coax tap to the BNC connector. BNC Connector 31459-M 6. Terminate any unused coax ports by connecting a 75 Ω terminator to the unused BNC connector.
  • Page 16: Status Indicators

    16 ControlNet Modular Repeater Adapter Status Indicators The status indicators on the repeater adapter module can be interpreted alone or together. Repeater Modules Repeater Adapter 31453-M The following three tables list different combinations of status indicators and their interpretations. Status Indicators Page Power-up and fault conditions Table 1...
  • Page 17 ControlNet Modular Repeater Adapter 17 Table 1 -Power-up and Fault Conditions Indicator Description Action Alternating Repeater adapter module is being Do nothing. The repeater adapter red/green powered-up or reset. module is operating properly. Solid red A jabber condition has occurred. Check the network and Another node or repeater on the components for proper operation.
  • Page 18 18 ControlNet Modular Repeater Adapter Table 3 -Repeater Modules Status Indicator Indicator Description Action Solid green Error-free data is being recovered Do nothing. This is the normal at all of the attached repeater operating mode. modules. Flashing Data with errors is occasionally •...
  • Page 19: Specifications

    ControlNet Modular Repeater Adapter 19 Specifications Technical Specifications - 1786-RPA/B Attribute 1786-RPA/B Power consumption, max 16.8 W Power dissipation, max 8.8 W Input voltage rating, max 700 mA @ 24V DC, Class 2/SELV Input voltage range 18…36V DC Backplane output current, max 1.6A @ 5V DC Minimum enclosure size (HxWxD), approx 304.8 x 196.8 x 101.6 mm...
  • Page 20 20 ControlNet Modular Repeater Adapter Environmental Specifications - 1786-RPA/B Attribute 1786-RPA/B Temperature, operating 0…60 °C (32…140 °F) IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max 60 °C (140 °F) Temperature, nonoperating -40…85 °C (-40…185 °F)
  • Page 21 ControlNet Modular Repeater Adapter 21 Environmental Specifications - 1786-RPA/B Attribute 1786-RPA/B Radiated RF immunity 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at IEC 61000-4-3 900 and 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz EFT/B immunity ±4 kV at 5 kHz on power ports...
  • Page 22 22 ControlNet Modular Repeater Adapter Certifications - 1786-RPA/B Certification 1786-RPA/B European Union 2004/108/EC EMC Directive, compliant with the following: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A &...
  • Page 23: Additional Resources

    ControlNet Modular Repeater Adapter 23 Additional Resources These documents contain additional information concerning related Rockwell Automation products. Resource Description ControlNet Coax Taps Installation Document contains procedures and Instructions, publication 1786-IN007 specifications for the installation of ControlNet coaxial taps. ControlNet Coax Media Planning and Document describes the components and Installation Guide, publication CNET-IN002...
  • Page 24 RA-DU002, available at http://www.rockwellautomation.com/literature/. Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400...