Install Modbus Server On Your Linpac/ / / / Lincon; Software Installation - ICP DAS USA LinPAC-8000 User Manual

Table of Contents

Advertisement

Modbus RTU/TCP Server User Manual for LinPAC / LinCon
1-1. Install Modbus server on your LinPAC/ / / / LinCon

Software Installation

If your LinPAC/LinCon is former released, you have to install the Modebus Server by
manual.
STEP 1 :
Download the latest Modbus Server for LinPAC/LinCon.
http://www.icpdas.com/download/download-list.htm
STEP 2 :
Copy the "mbserver10" file to your LinPAC/LinCon, and change the file permission
to "755" or above.
#chmod 755 ./mbserver10
STEP 3 :
Before executing LinPAC/LinCon Modbus Server, you have to check what's the
index number of your TTY devices.
#dmesg | grep 'ttyS'
In general, LinCon support 2 serial ports,
ttyS0 :COM2 RS-232 (Recommend!)
ttyS1 :COM3 RS-485
and 3 serial ports are availabled on LinPAC.
ttyS0 :COM1, RS232 (Reserved for console terminal)
ttyS1 :COM3, RS232/RS-485
ttyS34 :COM4, RS232 (Recommend!)
STEP 4 :
You can use following command to start Modbus Server.
#./mbserver10 [Device Net ID] [COM port Index number]
For example :
#./mbserver10 4 0
#./mbserver10 9 34
To check the command usage :
#./mbserver10
Ver : 1.0
(2009.04)
Start Modbus Server for ttyS0, and the Device ID = 4
Start Modbus Server for ttyS34, and the Device ID = 9
4