Technical Specifications

T
ECHNICAL

Environmental Requirements

Operating Conditions

Wiring
• Control Cabling 0.75sq.mm minimum.
• Power cable to be minimum 600V AC rated at 1.5 x armature current.
• High speed semi-conductor fuses of the correct rating are recommended controller semi-
• Ensure a protective earth connection is made compatible with the rating.
• Isolated control wiring should not be run close to the power cabling. If screened cables are
• Parker SSD Drives can supply fuse assemblies which can be bulkhead mounted and also act
S
PECIFICATIONS
Enclosure
Operating Temperature
Humidity
Altitude
Storage Temperature
Transport Temperature
Climatic Conditions
Installation Category
Pollution
Maximum Supply Voltages
(Derived from a 3-phase
supply)
conductor protection, as the 512C is not internally fused. The suitability of the semi-
conductor fuse branch protection should be decided by the installer.
used (recommended on setpoints and tachogenerators) connect screens to earth only at
controller end.
as convenient supply isolators.
www.comoso.com
Chassis Mounting IP00.
0 to +40 o C. (Derate 1.5%/Degree above
40 o C)
85% R.H. at 40 o C. (non condensing)
Above 1000m derate at 1% / 100m.
-25 o C to +55 o C
-25 o C to +70 o C
Class 3k3, as defined by EN50178 (1998)
Overvoltage Category III
Pollution Degree 2.
480Vac L - L
Non earth referenced (IT)
or earth referenced (TN)
480Vac L - N
Earth referenced (TN)