Operating The Converter; Pre-Installation Planning; Basic Wiring Diagrams; Basic Connection - Parker 512C Series Technical Manual

Hide thumbs Also See for 512C Series:
Table of Contents

Advertisement

4-1

Operating the Converter

O
PERATING THE

Pre-Installation Planning

Basic Wiring Diagrams

23
19
16
15
14
3
10K
SPEED
SETPOINT
Health
Relay
Speed
Relay
C
ONVERTER

Basic Connection

Signal Ground
2
13
12
11
10
9
8
7
6
5
10K
100%
EXTERNAL
CURRENT
LIMIT
10K
(Optional)
RUN
When the mains voltage is non-standard, i.e. not selectable via the transformer tapping link
(380/415V, 220/240V or 110/120V), connect a low power Autotransformer to generate a
standard voltage. Connect the output of the Autotransformer to the AUX terminal. Move the
Supply Selector from "MAINS" to "AUX". Select the appropriate voltage via the transformer
tapping link. The Autotransformer must be connected to the same phase as the incoming
power to provide correct coding to the controller.
It is recommended that the "0V/common" be connected to protective earth/ground for safety
reasons. In a system comprising of more than one controller, the "0V/common" signals
should be connected together and joined to protective earth/ground at one point only.
Stall override link between terminals 14 and 15 required when using controller in current
control.
www.comoso.com
Mains Supply
Branch Protection (Fuses or Circuit Breaker)
FS1
FS2
FS4
4
3
1
L1
L2/N
FL1
FL2
PE
GND
Autotransformer
1
1
PE
standard
FS5
GND
voltage
A+
A-
Aux
F+
F-
DC
Motor
Tachogenerator
Optional
512C Series Converter