CHAPTER B: IEC 61850 IMPLEMENTATION DETAILS

PIXIT for Control model

ID
Ed
Description
Ct1
-
What control models are supported
(compare PICS)
Ct2
1,2
Is the control model fixed, configurable and/or dynamic
Ct3
-
Is TimeActivatedOperate supported (compare PICS or SCL)
Ct4
-
Is "operate-many" supported (compare sboClass)
Ct5
1
Will the DUT activate the control output when the test attribute is set in
the SelectWithValue and/or Operate request (when N test procedure Ctl2
is applicable)
Ct6
-
What are the conditions for the time (T) attribute in the SelectWithValue
and/or Operate request
Ct7
-
Is pulse configuration supported (compare pulseConfig)
Ct8
1
What is the Behavior of the DUT when the check conditions are set
Is this Behavior fixed, configurable, online changeable
Ct9
1,2
Which additional cause diagnosis are supported
Ct10 1,2
How to force a "test-not-ok" respond with SelectWithValue request
Ct11 1,2
How to force a "test-not-ok" respond with Select request
Ct12 1,2
How to force a "test-not-ok" respond with Operate request
Ct13 1,2
Which origin categories are supported / accepted
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
Value / Clarification
Deprecated
Configurable & Dynamic
Deprecated
Deprecated
N
Deprecated
Deprecated
N synchrocheck
N interlock-check
DUT ignores the check value and always
perform the check
Y Unknown
Y Not-supported
Y Blocked-by-switching-hierarchy
N Select-failed
Y Invalid-position
Y Position-reached
N Step-limit
Y Blocked-by-Mode
N Blocked-by-process
N Blocked-by-interlocking
N Blocked-by-synchrocheck
Y Command-already-in-execution
N Blocked-by-health
N 1-of-n-control
N Abortion-by-cancel
Y Time-limit-over
N Abortion-by-trip
Y Object-not-selected
Edition 1 specific values:
N Parameter-change-in-execution
Edition 2 specific values:
Y Object-already-selected
N No-access-authority
N Ended-with-overshoot
N Abortion-due-to-deviation
N Abortion-by-communication-loss
N Blocked-by-command
N None
Y Inconsistent-parameters
Y Locked-by-other-client
N Parameter-change-in-
execution
Device in local mode
DOns: Sending T=1
SBOns: Sending T=1
DOes: Sending T=1
SBOes: Sending T=1
N bay-control
Y station-control
Y remote-control
N automatic-bay
Y automatic-station
Y automatic-remote
N maintenance
N process
PIXIT