THE IEC 61850 CONFIGURATOR

Goose Reception

8-22
Figure 8-19: Dataset Properties
The 8 Series relay can receive Transmitted GOOSE from any IED in "GOOSE Reception". For
proper GOOSE reception the relay must be configurated as described in this section. A
maximum of eight IEDs can be added.
GOOSE Reception has two sections:
IDE list: The user can add IED to subscribe GOOSE.
Mapping to Remote Inputs: Each subscribed GOOSE dataset item can be appended in
the screen using the drag and drop method.
Figure 8-20: Goose Reception Screen
The following buttons are available in the Goose Reception window:
"Add IED" button and "Remove IED" button: Both buttons are in the lower side of the
screen.
Note that IED can also be added by right clicking in the "IED List" section.
The "Remove IED" button deletes a configured IED.
Save button and Cancel button: Click the Save button to save all configured settings.
Click the Cancel button to discard the modifications just made to the configuration.
Configure Dataset Items
1.
Select the dataset item being subscribed under the required IED which is available in
Template > LDInst > GOOSEOut 1 tree.
2.
Go to the required dataset item.
3.
Drag and drop the chosen dataset item to the "Mapping to Remote Inputs" section as
shown in the figure: Mapping to Remote Inputs.
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 8: IEC 61850