CHAPTER 8: IEC 61850

Reports

8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
These GGIO1 indications are assigned by the corresponding setpoint that can be
modified in the "Settings Tab" screen of the 61850 configurator. There, the user can
select the mapping element from the FlexLogic™ operand list similar to DNP or IEC104
binary input point configuration.
The Reports tab in IEC 61580 Configurator permits configuration of data sets and report
control blocks for buffered and unbuffered reports.
Figure 8-1: Reports Screen
The screen helps the user to create, modify and delete Report Control Blocks (RCBs) and
Datasets. Each Report Control Block must have a maximum of 4 different clients up to a
maximum of 4 Report Control Blocks linked to their Datasets. Each dataset must have a
maximum of 64 elements in total.
There are two screens available in the Report tab window:
Report control block: The user can add the required report control block.
RCB Name: The first character in the value of this attribute must be a letter (upper
or lower case). The rest of the characters must be a number, a letter (upper or
lower case) or a "_". The maximum number of characters allowed in IEC61850
Configurator is 30 and IEC61850 MMS Library adds 2 more characters indicating
the number of the instance of the RCB depending on the number of IEC61850
clients configured.
Description: The maximum number of characters allowed is 32.
Dataset sources: Each report control block can be appended with dataset items in the
screen using a drag and drop operation.
THE IEC 61850 CONFIGURATOR
8-13