CHAPTER 12: ABOUT THE MODBUS MEMORY MAP

Compatibility Mode

8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
The 8 Series relay supports emulation of the SR750/SR469 Modbus memory map for
retrofit applications. The emulation supports typical actual value data for common data
items. When enabled, the 8 Series relay responds to Modbus packets from a PLC as if it
were a legacy SR relay.
The compatibility mode is only available for RS485 and rear Ethernet ports. (The USB and
Wifi always respond using the 8 Series memory map.)
When in compatibility mode, the rear Ethernet ports support setting changes for
Compatibility mode, Set date and time, Clear events, and Event retrieval.
User Map
When using the default user map in compatibility mode, the user is required to enter the
Modicon format for the address that is being read in the user map. The Modicon format
has an offset of 30001, and thus is different from the values found in the SR publications.
For convenience, the translated values have been included in the tables below. The user
map can only be entered in an offline file, and the compatibility mode must be set to
SR469 or SR750, depending on the product being used.
The user map implementation is the same function as covered in the section Accessing
Data via the User Map. The only difference is that the read function starts at 0100h (256
Dec) to correspond to the SR469/SR750 map.Range: User Map #1 (0100h) to User Map
#125 (017Ch)
Example:
PLC requests Phase A current from SR469 = 0300h (HEX) using User Map #1 = 0100h
Default User Map #1 in 8 Series PC SW = 30769 (Dec) => SR469 = 768 (Dec) = 0300h(HEX)
The following tables list the addresses supported in compatibility mode for both SR469 and
SR750. The SR Hex and decimal values are provided with the corresponding 8 Series value.
Table 12-3: SR469 Addresses supported in Compatibility Mode
469 HEX
469 Decimal
0000
0
0001
1
0002
2
0010
16
00F0
240
00F2
242
0201
513
0202
514
0204
516
0211
529
0300
768
0302
770
0304
772
0306
774
0308
776
0309
777
030A
778
030B
779
030D
781
Modicon Format
Description
(Needed for User Map)
30001
Product Code
30002
Hardware Revision
30003
Firmware Version
30017
Boot
30241
Time
30243
Date
30514
Motor Thermal Capacity Used
30515
Estimated Trip Time on OL
30517
Motor Speed
30530
CO Outputs
30769
J1 Ia RMS
30771
J1 Ib RMS
30773
J1 Ic RMS
30775
J1 I AVG
30777
Motor Load
30778
Motor Current Unbalance
30779
Therm Model Biased Load
30780
J1 Ig RMS
30782
Ia Diff
COMPATIBILITY MODE
12-3