REAL-TIME CLOCK

Clock

3-4
PTP VLAN ID
Range: 0 to 4095
Default: 0
The setting selects the value of the ID field in the 802.1Q VLAN tag in request messages
issued by the relay's peer delay mechanism. It is provided in compliance with PP (Power
Profile). As these messages have a destination address that indicates they are not to be
bridged, their VLAN ID serves no function, and so may be left at its default value.
Depending on the characteristics of the device to which the relay is directly linked, VLAN
ID may have no effect.
The setting applies to all of the relay's PTP-capable ports.
PTP PRIORITY
Range: 1, 2
Default: 1
The setting sets the priority of PTP time for the relay. If set to 1 and IRIG-B is available,
the relay syncs the relay's time reference to the PTP time. If set to 2 and IRIG-B is
available, the relay syncs its reference to IRIG-B time.
Path:
Setpoints > Device > Real Time Clock > Clock
DATE
Format: Month/Day/Year
Range: Month: 1 to 12; Day: 1 to 31; Year: 2008 to 2094
Default: 01/01/2008
TIME
Range: 0 to 23: 0 to 59:0 to 59
Default: 00:00:00
LOCAL TIME OFFSET FROM UTC
Range: –24.0 to 24.0 hrs in steps of 0.5 hrs
Default: 0.0 hrs
REAL TIME CLOCK EVENTS
Range: Disabled, Enabled
Default: Enabled
IRIG-B
Range: Disabled, Enabled
Default: Disabled
DAYLIGHT SAVINGS TIME
Range: Disabled, Enabled
Default: Disabled
DST START MONTH
Range: January to December (all months)
Default: Not Set
DST START DAY
Range: SUN to SAT (all days of the week)
Default: Not Set
DST START WEEK
Range: 1st, 2nd, 3rd, 4th, Last
Default: Not Set