CHAPTER B: IEC 61850 IMPLEMENTATION DETAILS

PIXIT for GOOSE publish model

ID
Ed
Description
Gp1
1,2
Can the test (Ed1) / simulation (Ed2) flag in the
published GOOSE be set
Gp2
1
What is the Behavior when the GOOSE publish
configuration is incorrect
Gp3
1,2
Published FCD supported common data classes
are
Gp4
1,2
What is the slow retransmission time
Is it fixed or configurable
Gp5
1,2
What is the fastest retransmission time
Is it fixed or configurable
Gp6
-
Can the GOOSE publish be turned on / off by using
SetGoCBValues(GoEna)
Gp7
1,2
What is the initial GOOSE sqNum after restart
Gp8
1
May the GOOSE data set contain:
- structured data objects (FCD)
- timestamp data attributes
Gp9
2
How is the retransmission curve after a change.
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
Value / Clarification
N
DUT keeps GoEna=F
Configuration tool does not allow wrong configuration to be
uploaded into device. e.g.: empty dataset.
SPS, INS, ENS, ACT, ACD, MV, CMV, SAV, WYE, DEL, SEQ, INC, ENC, SPC,
DPC, INC, ENC. (Only the elements with FC=ST or MX will be
published).
Configured by SCL on GoCB MaxTime
Fixed. MinTime = 5 ms
Y
sqNum = 1
Y
Y (timestamp attributes are not supported)
- sqNum = 0 New change
- sqNum = 1 -> 5ms later with TAL = 1000
- sqNum = 2 -> 10ms later with TAL = 1000
- sqNum = 3 -> 15ms later with TAL = 4000
- sqNum = 4 -> 1000ms later with TAL = Update time* x 4
- sqNum = 5 -> Update time* later with TAL = Update time* x 4
- sqNum = 6-> Update time* later with TAL = Update time* x 4
- sqNum = 7 ........
- .............
*Update time is configured in the Enervista 8 Series Setup