CHAPTER 8: IEC 61850
FASTPATH:

IEC 61850 Configurator Details

8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
Read Device Settings: The menu option reads all the settings from the relay by TFTP
and creates an 8 Series relay file with extension *.CID. The created *.CID file consists of
two sections. A private section where all non IEC 61850 settings are available, and a
public section in which IEC 61850 related settings are implemented.
When creating a CID file using a 3rd party ICT/SCL tool, the user must ensure the following:
The order code in the CID file must match the device order code if writing the CID
file directly into the relay (without using the EnerVista software). The "Desc" value
in communication settings of the CID file must match the relay's order code.
The maximum allowed services must be equal or below the specified limits as in
ICD/CID.
Configure Datasets only in "LLN0" logical node.
Creating new LD, LN, and communication-AP settings is not recommended.
OFFLINE SETTINGS FILE
The Generate ICD file menu option generates a default ICD file with the respective order
code option and saves the file to the path the user has selected previously.
The IEC61850 Configurator allows the user to edit all sections of the IEC61850 CID and ICD
file. The user cannot perform any other operations in the EnerVista 8 Series Setup software
if the IEC 61850 Configurator is open. The user must close the IEC61850 session to perform
other operations in the EnerVista software.
The IEC 61850 configurator consists of five sections:
ICD/CID
Settings
Reports
GOOSE Reception
GOOSE Transmission
THE IEC 61850 CONFIGURATOR
8-7