Goose Status - GE Multilin 850 Communications Manual

Protective relay platform 8 series
Table of Contents

Advertisement

STATUS

GOOSE Status

8-4
CLIENT 1(8) IP ADDRESS
Range: 0, 0XFFFFFFFF
Default: 0
GGIO1 INDICATIONS
Path:
Status > Communications > GGIO1 Indications
The present state of the 32 GGIO1 Indications are shown here. There are up to 32 GGIO
indications that can be used to map any FlexLogic operand into the IED 61850 information
model. Default value is Off.
GOOSE STATUS
Path:
Status > Communications > GOOSE Status
GOOSE 1 to 64 Status
Range: OFF, ON
Default: OFF
GOOSE HEADER
Path:
Status > Communications > GOOSE HDR Status
GOOSE 1 to 64 H.Status
Range: OFF, ON
Default: OFF
GOOSE ANALOG
Path:
Status > Communications > GOOSE Analog AV
FLOAT 1 to 24
Range:
Default: 0.0
SINT32 1 to 8
Range:
Default: 0
IEC 61850 STATUS
Path:
Status > Communications > IEC 61850 Status
COMMS NOT VALIDATED OK
Range: NO, YES
Default: NO
COMMS NOT VALIDATED DONE
Range: YES, NO
Default: YES
COMMS VALIDATED OK
Range: YES, NO
Default: YES
COMMS VALIDATED DONE
Range: YES, NO
Default: YES
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 8: IEC 61850