Altitude/Temperature Correction Factors Table

Air
Temp.
0
1000
40
1.060
1.022
50
1.039
1.002
60
1.019
0.982
70
1.000
0.964
80
0.982
0.947
90
0.964
0.929
100
0.946
0.912
1.100
1.050
1.000
0.950
0.900
0.850
0.800
0.750
0.700
0.650
0.600

Altitude/Temperature Correction Factors Figure

The examples below will assist in determining the airflow
performance of the product at altitude.
Example 1: What are the corrected CFM, static pressure,
and BHP at an elevation of 5,000 ft. if the blower
performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution: At an elevation of 5,000 ft. the indoor blower will still
deliver 6,000 CFM if the rpm is unchanged. However, the
Altitude/Temperature Correction Factors table must be used to
determine the static pressure and BHP. Since no temperature
data is given, we will assume an air temperature of 70°F. The
table shows the correction factor to be 0.832.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Corrected BHP = 4.0 x 0.832 = 3.328
Example 2: A system, located at 5,000 feet of elevation, is to
deliver 6,000 CFM at a static pressure of 1.5". Use the unit
60
2000
3000
4000
0.986
0.950
0.916
0.966
0.931
0.898
0.948
0.913
0.880
0.930
0.896
0.864
0.913
0.880
0.848
0.897
0.864
0.833
0.880
0.848
0.817
40
50
60
Air Temperature (ºF)
Altitude (Ft.)
5000
6000
7000
0.882
0.849
0.818
0.864
0.832
0.802
0.848
0.816
0.787
0.832
0.801
0.772
0.817
0.787
0.758
0.802
0.772
0.744
0.787
0.758
0.730
70
80
90
blower tables to select the blower speed and the BHP
requirement.
Solution: As in the example above, no temperature
information is given so 70°F is assumed.
The 1.5" static pressure given is at an elevation of 5,000 ft.
The first step is to convert this static pressure to equivalent
sea level conditions.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
BHP at 5,000 ft. = 3.2 x .832 = 2.66
8000
9000
10000
0.788
0.758
0.729
0.772
0.743
0.715
0.757
0.729
0.701
0.743
0.715
0.688
0.730
0.702
0.676
0.716
0.689
0.663
0.703
0.676
0.651
Sea Level
1000 ft
2000 ft
3000 ft
4000 ft
5000 ft
6000 ft
7000 ft
8000 ft
9000 ft
10000 ft
100
Johnson Controls Unitary Products

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents