Air Handling And Hot Water Coil Accessory Heating Capacity; Nc300 / 1Hw0406; Hot Water Coil Capacity Correction And Pressure Drop Vs Gpm - York R-410A Technical Manual

Split-system air-cooled condensing units and air handlers
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

Air Handling and Hot Water Coil Accessory Heating Capacity

1

NC300 / 1HW0406

UNIT
HOT WATER
MODEL
COIL MODEL
NC300
1HW0406
1
These capacities do not include any blower motor heat.
NOTE: Temperature Water Drop (ºF) = (2 X MBH) / GPM.

Hot Water Coil Capacity Correction And Pressure Drop Vs GPM

HOT WATER COIL MODEL
1HW0406
1
For pressure drop in feet (water), multiply these values by 2.31.
Air Handling and Steam Coil Accessory Heating Capacity
NC300 / 1NF0454
UNIT
STEAM COIL
MODEL
MODEL
NC300
1NF0454
1
These capacities do not include any blower motor heat.
Steam Coil Capacity Correction Factors For High Steam Pressure
STEAM PRESSURE (PSIG)
CAPACITY CORRECTION FACTOR
NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH
Johnson Controls Unitary Products
GPM
CFM
ENTERING WATER TEMPERATURE MINUS ENTRY AIR TEMPERATURE °F.
70
6,000
204
8,000
236
50
10,000
265
12,000
291
GPM
25
50
75
100
CFM
6,000
8,000
10,000
12,000
5
1.05
CAPACITY (MBH)
90
110
263
325
304
372
341
416
374
457
1
PRESSURE DROP
PSI
0.4
1.0
1.8
3.4
CAPACITY (MBH) @ 2 PSIG
DRY BULB TEMPERATURE OF AIR ENTERING COIL (°F)
10
30
471
424
535
483
592
535
642
580
10
15
1.12
1.19
505428-YTG-V-0417
130
150
384
443
440
508
492
568
540
623
CAPACITY CORRECTION
FACTOR
0.79
1.00
1.04
1.07
1
50
70
380
330
432
380
478
422
518
456
20
25
1.25
1.30
51

Hide quick links: