York R-410A Installation Manual

York R-410A Installation Manual

R-410a outdoor split-system air conditioning 2 to 5 tons
Hide thumbs Also See for R-410A:

Advertisement

INSTALLATION MANUAL
R-410A
OUTDOOR SPLIT-SYSTEM
AIR CONDITIONING
MODELS: 15 SEER - CZE / AC5B / AL5B SERIES
2 TO 5 TONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATIONS REQUIRING TXV . . . . . . . . . . . . . . . . . . . . . . . . . . 4
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
R-410A Saturation Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
15Z24AC Subcooling Charging Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
15Z36AC Subcooling Charging Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Tubing Hanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Typical Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CFM Selection Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for the highest sales volume evaporator plus 15 feet of
field supplied lines.
Matching indoor coils are available with a thermal expansion valve or
an orifice liquid feed sized for the most common usage. The orifice size
and/or refrigerant charge may need to be changed for some system
combinations, elevation differences, or total line lengths. See tabular
data sheet provided in unit literature packet for charge requirements.
Refer to Application Data covering "General Piping Recommendations
and Refrigerant Line Length" (Part Number 036-61920-001).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.

TABLE OF CONTENTS

EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
SYSTEM START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
LIST OF TABLES
15Z48AC Subcooling Charging Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
15Z60AC Subcooling Charging Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Diagnostic Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
LIST OF FIGURES
Non-Variable Speed Furnace (Y1 & Y2 Connection) . . . . . . . . . . . . . . . . . . . . . 6
Typical Variable Speed Furnace/Air Handler Wiring . . . . . . . . . . . . . . . . . . . . . 6
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service, or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer, or service agency.
This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.
R-410A systems operate at higher pressures than R-22 systems.
Do not use R-22 service equipment or components on R-410A
equipment. Service equipment
INSPECTION
As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier's delivery receipt. A separate request for
inspection by the carrier's agent should be made in writing. See Local
Distributor for more information.
R
P
CERTIFICATION APPLIES ONLY
WHEN THE COMPLETE
SYSTEM IS LISTED
WITH ARI.
This product was manufactured
LISTED
in a plant whose quality system
is certified/registered as being
in conformity with ISO 9001.
Must Be Rated
for R-410A.
66901 / 035-20393-001 Rev. C (1204)

Advertisement

Table of Contents
loading

Summary of Contents for York R-410A

  • Page 1: Table Of Contents

    R-410A Saturation Properties ........
  • Page 2: Unit Installation

    Local Safety Codes and the limitations listed below: and performance. Limitations for the indoor unit, coil, and appropriate accessories Change-out of the indoor coil to an approved R-410A coil with the must also be observed. appropriate metering device. Only variable speed air handlers or variable speed furnaces Change-out of the line-set when replacing an R-22 unit with an should be used with these models.
  • Page 3: Tubing Hanger

    R-410A. If you are unsure, consult the equipment manufacturer. FIGURE 3: Underground Installation Never install a suction-line filter drier in the liquid line of an R-410A PRECAUTIONS DURING BRAZING OF LINES system. Failure to follow this warning can cause a fire, injury or death.
  • Page 4: Installations Requiring Txv

    66901 / 035-20393-001 Rev. C (1204) Protect the vapor valve with a wet rag and braze the vapor line connection to the outdoor unit. The nitrogen flow should be exiting the system from the vapor service port connection. After this con- nection has cooled, remove the nitrogen source from the liquid fit- Dry nitrogen should always be supplied through the tubing while it ting service port.
  • Page 5: Electrical Connections

    66901 / 035-20393-001 Rev. C (1204) Install TXV equalizer line in 1/8” hole previously made in vapor Remove the service access panel to gain access to the unit wiring. line. Equalizer line should not be bottomed out in the vapor line. Route wires from disconnect through power wiring opening pro- Insert equalizer line at least 1/4”...
  • Page 6: Single Stage Non-Variable Speed Furnace (Y Connection Only)

    66901 / 035-20393-001 Rev. C (1204) VARIABLE VARIABLE 2 -STAGE SPEED SPEED 2-STAGE THERMOSTAT AIR CONDITIONER AIR HANDLER THERMOSTAT FURNACE AIR CONDITONER BLU/YEL BLU/YEL HUMIDISTAT CONTACTS OPEN ON HUMIDITY RISE. HUMIDISTAT CONTACTS OPEN ON HUMIDITY RISE. HUMIDISTAT REMOVED JUMPER ON CFM SELECTION BOARD MUST BE HUMIDISTAT REMOVED JUMPER ON CFM SELECTION BOARD MUST BE...
  • Page 7: Evacuation

    6°F below the room tem- perature. R-410A refrigerant cylinders are rose colored, and have a dip tube which allows liquid to flow out of the cylinder in the Upright Posi- Operate the system for a minimum of 15-20 minutes.
  • Page 8: R-410A Saturation Properties

    REPAIR, SERVICE, MAINTENANCE OR THE FINAL DIS- POSAL OF THIS UNIT. WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE THE OWNER’S APPROVAL. TABLE 1: R-410A Saturation Properties PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE TEMP.
  • Page 9: 15Z24Ac Subcooling Charging Chart

    66901 / 035-20393-001 Rev. C (1204) TABLE 2: 15Z24AC Subcooling Charging Chart TABLE 4: 15Z48AC Subcooling Charging Chart Indoor Wet Bulb (°F) Indoor Wet Bulb (°F) Outdoor Outdoor Ambient Ambient DB (°F) Liquid Pressure (psig) at Base Valve DB (°F) Liquid Pressure (psig) at Base Valve 234 (10) 235 (11)
  • Page 10: Diagnostic Label

    66901 / 035-20393-001 Rev. C (1204) TRIP LED (Red): indicates there is a demand signal from the thermo- Comfort Alert Diagnostics — The Comfort Alert diagnostics stat but no current to the compressor is detected by the module. The module facilitates troubleshooting heat pump and air conditioning sys- TRIP LED typically indicates the compressor protector is open or may tem failures.
  • Page 11: Wiring Diagram

    66901 / 035-20393-001 Rev. C (1204) SECTION IX: WIRING DIAGRAM FIGURE 10: Wiring Diagram Unitary Products Group...
  • Page 12 Subject to change without notice. Printed in U.S.A. 66901 / 035-20393-001 Rev. C (1204) Copyright © by York International Corp. 2004. All rights reserved. Supersedes: 035-20393-001 Rev. A (0704) Unitary 5005 Norman Product York Group Drive 73069...