York AFFINITY SERIES R-410A Installation Manual

York AFFINITY SERIES R-410A Installation Manual

R-410a affinity series 2-4 ton
Hide thumbs Also See for AFFINITY SERIES R-410A:
Table of Contents

Advertisement

R-410A
AFFINITY SERIES
DNX024-048
2-4 Ton
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rigging And Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Power And Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . 10
Compressors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1 Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Unit Accessory Weights . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7 Natural Gas Pipe Sizing Chart . . . . . . . . . . . . . . . . . . . . 16
8 Propane (LP) Gas Pipe Sizing Chart . . . . . . . . . . . . . . . 16
1 Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Dimensions Front and Bottom . . . . . . . . . . . . . . . . . . . . . 8
5 Dimensions Back and Bottom . . . . . . . . . . . . . . . . . . . . . 8
6 Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Thermostat - Single Stage Gas Heat . . . . . . . . . . . . . . . 10
Thermostat - Two Stage Gas Heat . . . . . . . . . . . . . . . . 11
Thermostat - Single Stage Gas Heat . . . . . . . . . . . . . . . 11

General

®
YORK
Affinity Model DNX units are cooling/heating air
conditioners designed for outdoor installation. Only gas piping,
electric power and duct connections are required at the point of
installation.
The single or two stage gas-fired heaters have spark to pilot
ignition. The tubular heat exchangers are aluminized steel.
The refrigerant system is fully charged with R-410A Refrigerant,
and is tested and factory sealed.

TABLE OF CONTENTS

Phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Flue Vent Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Blower Speed Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Heating Sequence Of Operation . . . . . . . . . . . . . . . . . . . . 22
Cooling Sequence Of Operations . . . . . . . . . . . . . . . . . . . 24
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Adjustment of Temperature Rise . . . . . . . . . . . . . . . . . . . 27
Checking Gas Heat Input . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Natural Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
LIST OF TABLES
13 Side Duct Application . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
14 Bottom Duct Application . . . . . . . . . . . . . . . . . . . . . . . . . 19
15 Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . 21
16 Indoor Blower Specifications . . . . . . . . . . . . . . . . . . . . . . 21
17 Delay Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
18 Ignition Control Board FLASH CODES . . . . . . . . . . . . . . 24
19 Gas Rate Cubic Feet Per Hour . . . . . . . . . . . . . . . . . . . . 27
LIST OF FIGURES
Thermostat - Two Stage Gas Heat . . . . . . . . . . . . . . . . 12
11 Typical Field Power Wiring Diagram . . . . . . . . . . . . . . . 12
13 Flue Vent Outlet Air Hood . . . . . . . . . . . . . . . . . . . . . . . 16
14 Control Board Speed Tap Location . . . . . . . . . . . . . . . . 22
15 Single Stage Gas Valve Front . . . . . . . . . . . . . . . . . . . . 25
16 Two Stage Gas Valve Front . . . . . . . . . . . . . . . . . . . . . . 26
17 Single Stage Gas Valve Rear . . . . . . . . . . . . . . . . . . . . 26
18 Two Stage Gas Valve Rear . . . . . . . . . . . . . . . . . . . . . . 26
19 Proper Flame Adjustment . . . . . . . . . . . . . . . . . . . . . . . 26
20 R-410A Quick Reference Guide . . . . . . . . . . . . . . . . . . 36
Safety Considerations
This is a safety alert symbol
labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention the signal words
DANGER, WARNING or CAUTION.
DANGER indicates an imminently hazardous situation, which,
if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which,
if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if
not avoided may result in minor or moderate injury. It is also
used to alert against unsafe practices and hazards involving
only property damage.
SO 9001
Certified Quality
Management System
. When you see this symbol on

Advertisement

Table of Contents
loading

Summary of Contents for York AFFINITY SERIES R-410A

  • Page 1: Table Of Contents

    Thermostat - Single Stage Gas Heat ....11 General ® YORK Affinity Model DNX units are cooling/heating air conditioners designed for outdoor installation. Only gas piping, electric power and duct connections are required at the point of installation.
  • Page 2 • Technical Guide - DNX024-048, 291625 • General Installation - DNX024-048, 279550 Renewal Parts ® Contact your local York parts distribution center for authorized replacement parts. Approvals Design certified by CSA as follows: For use as a cooling only unit, cooling unit with supplemental electric heat or a forced air furnace.
  • Page 3: Installation

    279550-YIM-A-0207 For installation on combustible material and may be installed directly on combustible flooring or, in the U.S., on wood flooring or Class A, Class B or Class C roof covering materials. For use with natural gas (convertible to LP with kit). This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state, and national codes including, but not limited...
  • Page 4: Unit Limitations

    In Canada: Canadian Electrical Code, CSA C22.1 Installation Codes, CSA - B149.1. Local plumbing and waste water codes, and Other applicable local codes. Refer to unit application data found in this document. After installation, gas fired units must be adjusted to obtain a temperature rise within the range specified on the unit rating plate.
  • Page 5: Location

    If a unit is to be installed on a roof curb other than a ® York roof curb, gasketing must be applied to all surfaces that come in contact with the unit underside. Before lifting, make sure the unit weight is distributed equally on the rigging cables so it will lift evenly.
  • Page 6: Weights And Dimensions

    Figure 2: Unit 4 Point Load Weight Table 2: Weights and Dimensions Size Weight (lbs.) Center of Gravity (Tons) Shipping Operating (2.0) (3.0) (4.0) Table 3: Unit Accessory Weights Unit Accessory Model Add Economizer 4 Point Load Location (lbs.) 24.5 24.25 Weight (lbs.) Shipping...
  • Page 7: Unit Dimensions

    279550-YIM-A-0207 Unit Dimensions Figure 3: Table 4: Unit Dimensions Unit Size “A” 33-1/2 036, 048 41-1/2 Table 5: Unit Clearances Distance Direction (in.) Front Rear 1. A 1" clearance must be provided between any combustible material and the supply air duct work. 2.
  • Page 8: Dimensions Front And Bottom

    279550-YIM-A-0207 Figure 4: Dimensions Front and Bottom Figure 5: Dimensions Back and Bottom Unitary Products Group...
  • Page 9: Ductwork

    279550-YIM-A-0207 Figure 6: Roof Curb Ductwork These units are adaptable to downflow use as well as rear supply and return air duct openings. To convert to downflow, use the following steps: Remove the duct covers found in the bottom return and supply air duct openings.
  • Page 10: Service Access

    Service Access Access to all serviceable components is provided at the following locations: • Blower compartment access panel • Gas control/electrical access panel • Refrigerant connections Refer to Figure 3 for location of these access locations and minimum clearances in Table 5. This system uses R-410A Refrigerant which operates at higher pressures than R-22.
  • Page 11: Typical Field Control Wiring Diagram Single Stage Thermostat - Two Stage Gas Heat

    279550-YIM-A-0207 ** = Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire. PROGRAMMABLE THERMOSTAT ONLY Figure 8: Typical Field Control Wiring Diagram Single Stage Thermostat - Two Stage Gas Heat Figure 9: Typical Field Control Wiring Diagram Two Stage Thermostat - Single Stage Gas Heat Unitary Products Group SINGLE STAGE UNIT CONTROL BOARD...
  • Page 12: Electrical Data

    ** = Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire. PROGRAMMABLE THERMOSTAT ONLY Figure 10: Typical Field Control Wiring Diagram Two Stage Thermostat - Two Stage Gas Heat Figure 11: Typical Field Power Wiring Diagram Table 6: Electrical Data Compressors Size...
  • Page 13 279550-YIM-A-0207 DNX024-048 Single Stage Gas Heat Component DNX024 Nominal Tonnage ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 24.6 ARI net capacity (Btu) 24.0 11.5 SEER 15.0 Nominal CFM System power (KW) Refrigerant type R-410A Refrigerant charge (lb-oz) ARI HEATING PERFORMANCE Heating model Heat input (K Btu)
  • Page 14 DNX024-048 Two Stage Gas Heat Component DNX024 Nominal Tonnage ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 24.6 ARI net capacity (Btu) 24.0 11.5 SEER 15.0 Nominal CFM System power (KW) Refrigerant type R-410A Refrigerant charge (lb-oz) ARI HEATING PERFORMANCE Heating model Heat input (K Btu) 70/45.5...
  • Page 15: Compressors

    279550-YIM-A-0207 Compressors The scroll compressor used in this product is specifically designed to operate with R-410A Refrigerant and cannot be interchanged. This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system. The compressor also uses a polyolester (POE oil), Mobil 3MA POE.
  • Page 16: Natural Gas Pipe Sizing Chart

    Table 7: Natural Gas Pipe Sizing Chart Nominal Inches Iron Pipe Size Length In Feet 1/2” 3/4” 1. Maximum capacity of pipe in cubic feet of gas per hour (based upon a pressure drop of 0.3 inch water column and 0.6 specific gravity gas).
  • Page 17: Natural Gas Application Data-Single Stage

    279550-YIM-A-0207 Table 9: Natural Gas Application Data-Single Stage Available On Models 2 Ton 2 Ton 3,4 Ton 3 Ton 4 Ton 4 Ton 1. Heating capacity valid for elevations up to 2000 feet above sea level. For elevations above 2,000 feet, rated capacity should be reduced by 4% for each 1,000 feet above sea level.
  • Page 18: Airflow Performance

    Airflow Performance Table 13: Side Duct Application Size Thermostat Mode (Tons) Input Cool Y1+Y2 Y1+Y2 High Y1+Y2 Y1+Y2 N036 (2.0) N056 Heat D056 W1+W2 W1+W2 W1+W2 W1+W2 Cool Y1+Y2 Y1+Y2 High Y1+Y2 Y1+Y2 N065 (3.0) N090 Heat D090 W1+W2 W1+W2 W1+W2 W1+W2 Cool...
  • Page 19: Bottom Duct Application

    279550-YIM-A-0207 Table 13: Side Duct Application (Continued) Size Thermostat Mode (Tons) Input N065 N090 D090 W1+W2 W1+W2 Heat (4.0) W1+W2 W1+W2 N110 D110 W1+W2 W1+W2 W1+W2 W1+W2 Table 14: Bottom Duct Application Size Thermostat Mode (Tons) Input Cool Y1+Y2 Y1+Y2 High Y1+Y2 Y1+Y2...
  • Page 20 Table 14: Bottom Duct Application (Continued) Size Thermostat Mode (Tons) Input Cool Y1+Y2 Y1+Y2 High Y1+Y2 Y1+Y2 N065 (3.0) N090 Heat D090 W1+W2 W1+W2 W1+W2 W1+W2 Cool Y1+Y2 Y1+Y2 High Y1+Y2 Y1+Y2 N065 N090 (4.0) D090 W1+W2 W1+W2 Heat W1+W2 W1+W2 N110 D110...
  • Page 21: Blower Speed Selection

    279550-YIM-A-0207 Table 15: Additional Static Resistance Size Wet Indoor Coil (Tons) 0.01 0.01 0.01 0.02 (2.0) 0.03 1000 0.04 1100 0.05 1200 0.06 0.01 0.02 0.03 1000 0.04 (3.0) 1100 0.05 1200 0.06 1300 0.07 1400 0.08 1100 0.02 1200 0.03 1300 0.04...
  • Page 22: Operation

    The “Heat” Jumper on the CFM selection board should be set to “A”. Fan Only CFM: When the connection is made from “R” to “G”, the fan only mode is activated. In this mode, the blower will deliver 75% of the cooling system CFM.
  • Page 23 279550-YIM-A-0207 Main Burner Operation High Heat Warm-up Two stage models run high heat for the first 60 seconds following Pilot Flame Stabilization period regardless of W2 demand. If W2 is not energized at the end of this 60 second period the control de energizes the high gas output and steps the inducer to low speed.
  • Page 24: Cooling Sequence Of Operations

    Welded Gas Valve Relay Response. If either or both Pilot and Main Gas valve outputs are sensed to be off for more than 1 seconds when commanded to be on the control board shuts off all outputs and enters a hard lockout If the Pilot valve or Main valve output is sensed to be energized for more than 1 second when commanded to be off, the control de-energizes the induced draft motor (if flame is not present) to...
  • Page 25: Start-Up

    279550-YIM-A-0207 Circulating Fan When the thermostat calls for FAN, the thermostat terminal G is energized signaling the circulating fan to run at the heat speed 2 seconds after the G terminal is energized. If a call for HEAT occurs, the circulating fan continues to run at the heat speed.
  • Page 26: Two Stage Gas Valve Front

    Hi Fire (2nd Stage) Manifold Pressure Low Fire (1st Stage) Manifold Pressure Adjustment Manual Switch Pilot Adjustment (Remove Cap) Pilot Connect Figure 16: Two Stage Gas Valve Front ½ (Inlet) Figure 17: Single Stage Gas Valve Rear ½ (Inlet) Figure 18: Two Stage Gas Valve Rear Adjust as follows: Remove the cap from the valve body.
  • Page 27: Adjustment Of Temperature Rise

    279550-YIM-A-0207 Adjustment of Temperature Rise After about 20 minutes of high heat operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts about six feet from the furnace where they will not be affected by radiant heat. The temperature rise (or temperature difference between the return air and the heated air from the furnace) must lie within the range shown on the rating plate and the data in Tables 9...
  • Page 28: Typical Wiring Diagrams

    279550-YIM-A-0207 Typical Wiring Diagrams Typical DNX024 Cooling Unit with Single Stage Gas Heat 208/230-1-60 volt Wiring Diagram Unitary Products Group...
  • Page 29 279550-YIM-A-0207 Typical DNX024 Cooling Unit with Two Stage Gas Heat 208/230-1-60 volt Wiring Diagram Unitary Products Group...
  • Page 30 279550-YIM-A-0207 Typical DNX036-048 Cooling Unit with Single Stage Gas Heat 208/230-1-60 volt Wiring Diagram Unitary Products Group...
  • Page 31 279550-YIM-A-0207 Typical DNX036-048 Cooling Unit with Two Stage Gas Heat 208/230-1-60 volt Wiring Diagram Unitary Products Group...
  • Page 32 279550-YIM-A-0207 Typical DNX036-048 Cooling Unit with Single Stage Gas Heat 208/230-3-60 volt Wiring Diagram Unitary Products Group...
  • Page 33 279550-YIM-A-0207 Typical DNX036-048 Cooling Unit with Two Stage Gas Heat 208/230-3-60 volt Wiring Diagram Unitary Products Group...
  • Page 34 279550-YIM-A-0207 Typical DNX036-048 Cooling Unit with Single Stage Gas Heat 460-3-60 volt Wiring Diagram Unitary Products Group...
  • Page 35 279550-YIM-A-0207 Typical DNX036-048 Cooling Unit with Two Stage Gas Heat 460-3-60 volt Wiring Diagram Unitary Products Group...
  • Page 36: 410A Quick Reference Guide

    If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and replace all filter driers. Figure 20: R-410A Quick Reference Guide Subject to change without notice. Printed in U.S.A. Copyright © 2007 by Unitary Products Group. All rights reserved. Unitary Products Group 5005 York Drive 279550-YIM-A-0207 Supersedes: 98811-YIM-C-1006 Norman 73069...