505428-YTG-V-0417
YC120/NC120/NL120
(Continued)
Air on
Evaporator Coil
Total
Capacity
WB
CFM
(MBh)
(°F)
77
117.5
72
109.1
3000
67
100.8
62
94.0
57
94.0
77
124.2
72
115.4
3500
67
106.6
62
99.4
57
99.4
77
131.0
72
121.7
4000
67
112.3
62
104.8
57
104.8
72
124.7
67
115.2
4500
62
107.4
57
107.4
72
127.8
67
118.0
5000
62
110.1
57
110.1
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
20
Sensible Capacity (MBh)
Total
1
Input
Return Dry Bulb (°F)
2
(kW)
90
85
80
115°F
12.0
63.4
50.4
37.4
11.9
81.0
68.0
55.0
11.9
98.6
85.6
72.6
11.8
94.0
94.0
89.4
11.8
94.0
94.0
84.7
12.0
74.4
55.8
41.1
11.9
89.9
75.2
60.4
11.9
105.5
94.6
79.8
11.8
99.4
99.4
98.4
11.8
99.4
99.4
93.2
12.0
85.5
61.3
44.8
11.9
98.9
82.4
65.9
11.9
112.3
103.5
87.1
11.8
104.8
104.8
107.3
11.8
104.8
104.8
101.7
11.9
107.6
89.3
71.0
11.9
115.2
110.8
93.8
11.8
107.4
107.4
108.7
11.8
107.4
107.4
105.9
12.0
116.3
96.2
76.1
11.9
118.0
118.0
100.5
11.8
110.1
110.1
110.1
11.9
110.1
110.1
110.1
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
75
70
65
-
-
-
108.0
41.9
-
-
101.2
59.5
46.5
-
94.3
76.4
63.4 50.4
87.2
71.7
58.7 45.7
87.8
-
-
-
115.1
45.7
-
-
107.7
65.1
50.3
-
100.4
83.6
68.9 54.1
92.8
78.5
63.7 49.0
93.5
-
-
-
122.1
49.5
-
-
114.3
70.6
54.1
-
106.5
90.8
74.4 57.9
98.5
85.2
68.7 52.2
99.2
52.8
-
-
116.1
75.5
57.2
-
108.2
90.4
72.1 53.8
100.0
87.6
69.3 51.0
100.7
56.1
-
-
117.9
80.4
60.4
-
109.9
90.0
69.9 49.8
101.6
90.0
69.9 49.8
102.3
Sensible Capacity (MBh)
Total
Input
Return Dry Bulb (°F)
2
(kW)
90
85
80
125°F
13.2
60.3
47.2
34.1
13.2
78.4
65.3
52.2
13.1
94.3
83.4
70.3
13.0
87.2
87.2
85.1
13.1
87.8
87.8
77.8
13.2
73.6
53.0
38.1
13.2
87.9
73.1
58.2
13.1
100.4
93.2
78.3
13.0
92.8
92.8
92.8
13.1
93.5
93.5
86.9
13.2
86.9
58.7
42.1
13.2
97.5
80.8
64.2
13.1
106.5
103.0
86.3
13.1
98.5
98.5
98.5
13.1
99.2
99.2
95.9
13.2
106.1
87.5
68.9
13.1
108.2
108.2
92.6
13.1
100.0
100.0
100.0
13.1
100.7
100.7
99.1
13.2
114.7
94.1
73.6
13.1
109.9
109.9
98.9
13.0
101.6
101.6
101.6
13.1
102.3
102.3
102.3
nameplate rated motor
Johnson Controls Unitary Products
75
70
65
-
-
-
39.1
-
-
57.2
44.1
-
72.0
59.0 45.9
64.7
51.7 38.6
-
-
-
43.4
-
-
63.5
48.6
-
80.4
65.2 50.3
72.4
57.2 42.3
-
-
-
47.6
-
-
69.7
53.1
-
88.7
71.4 54.8
80.1
62.7 46.0
50.3
-
-
74.0
55.4
-
84.9
65.9 47.3
80.9
61.9 43.3
53.0
-
-
78.4
57.8
-
81.0
60.4 39.9
81.7
61.2 40.6

Hide quick links: