Siemens SIMATIC ET 200SP Manual page 34

Digital output module dq 4x24vdc/2a hf
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameter data record
A.1 Parameter assignment and structure of parameter data record
Error transmitting the data record
The module always checks all values of the data record to be sent. The module applies the
values from the data record only when all values have been transmitted without errors.
The WRREC instruction for writing data records returns the appropriate error code if there
are errors in the STATUS parameter.
The following table shows the module-specific error codes and their meaning for parameter
data record 128.
Error code in the STATUS pa-
rameter
(hexadecimal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
E0
DF
80
E1
34
Meaning
xx
Number of the data record unknown
xx
Length of the data record incorrect
xx
Slot invalid or unavailable
xx
Wrong version or error in the header in-
formation
xx
Parameter error
Solution
Enter valid number for data record.
Enter valid value for data record length.
Check the station to determine whether
the module is plugged in or pulled.
Check assigned values for the parame-
ters of the WREC instruction.
Correct the version, length and number of
parameter blocks.
Check the parameters of the module
Digital output module DQ 4x24VDC/2A HF (6ES7132-6BF20-0CA0)
Manual, 12/2015, A5E32855695-AC

Advertisement

Table of Contents
loading

Table of Contents