Siemens SIMATIC ET 200SP Manual page 15

Digital output module dq 4x24vdc/2a hf
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameter
Reaction to CPU
STOP
Potential group
Only when configuring using a PROFIBUS GSD file; does not apply to configuration with STEP 7 via HSP. The parame-
1
ter assignment options are limited because PROFIBUS GSD configuration limits the number of parameters to a maxi-
mum of 244 bytes for each ET 200SP station. If required, you can still assign the parameters using data records 64 to
67 as described in the column "GSD file PROFINET IO" (see table above). The parameter length of the I/O module is
7 bytes.
Note
If one of the two parameters "Diagnostics: Short-circuit to L+" or "Diagnostics: Wire break" is
enabled and one of these diagnostics occurs, the affected channel is switched off to avoid
triggering an undefined load. Note that a diagnostic interrupt can only be generated when
diagnostics are enabled.
as of module revision 04
1
Digital output module DQ 4x24VDC/2A HF (6ES7132-6BF20-0CA0)
Manual, 12/2015, A5E32855695-AC
Range of values
Turn off
Keep last value
Output substitute value 1
Use potential group of
the left module (module
plugged into a dark Ba-
seUnit)
Enable new potential
group (module plugged
into light-colored Ba-
seUnit)
1
Default
Parameter
reassignment
in RUN
Turn off
Yes
Use potential
No
group of the left
module
Parameters/address space
4.1 Parameters
Scope with configuration soft-
ware, e.g., STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Channel
Module
Module
Module
1
15

Advertisement

Table of Contents
loading

Table of Contents