Parameters/address space
4.3 Address space
2 x 2-channel configuration
For the configuration, the channels of the module are divided into multiple submodules. The
submodules can be assigned to different IO controllers when the module is used in a Shared
Device.
The number of usable submodules is dependent on the interface module used. Read the
information in the manual for the particular interface module.
Value status (quality information, QI)
The value status is always activated for the following module names:
● DQ 4×24VDC/2A HF QI
● DQ 4×24VDC/2A HF MSO
An additional bit is assigned to each channel for the value status. The bit for the value status
indicates if the output value specified by the user program is actually pending at the module
terminal (0 = value is incorrect).
Address space for configuration as 1 x 4-channel DQ 4×24VDC/2A HF V1.0
The figure below shows the address space assignment for configuration as a 4-channel
module without value status.
Image 4-1
18
Address space for configuration as 1 x 4-channel DQ 4×24VDC/2A HF, QI without value
status