socomec Green Power 2.0 60 Installation And Operating Manual
socomec Green Power 2.0 60 Installation And Operating Manual

socomec Green Power 2.0 60 Installation And Operating Manual

60-80 kva
Table of Contents

Advertisement

Green Power 2.0
Installations- und bedienungsanleitung
Installation and operating manual
Manuel d'installation et d'utilisation
Manuel d'installation et d'utilisation
Installatie– en bedieningshandleiding
Dokumentacja Techniczno-Ruchowa
Manual de instalação e funcionamento
Руководство по установке и эксплуатации
Navodila za priključitev in uporabo
Installations- och användarhandbok
6 0 - 8 0 k V A
Manual de instalación y uso
Paigaldus- ja kasutusjuhend
Manuale di installazione e uso
Manual de instalare şi utilizare
Kurulum ve kullanım kılavuzu
安装及操作手册
DE
EN
ES
ET
FI
FR
IT
NL
PL
PT
RO
RU
SL
SV
TR
ZH

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Green Power 2.0 60 and is the answer not in the manual?

Questions and answers

Summary of Contents for socomec Green Power 2.0 60

  • Page 1 Green Power 2.0 6 0 - 8 0 k V A Installations- und bedienungsanleitung Installation and operating manual Manual de instalación y uso Paigaldus- ja kasutusjuhend Manuel d’installation et d’utilisation Manuel d’installation et d’utilisation Manuale di installazione e uso Installatie– en bedieningshandleiding Dokumentacja Techniczno-Ruchowa Manual de instalação e funcionamento Manual de instalare şi utilizare...
  • Page 2 UPS inactivity. SOCOMEC may, at its own discretion, opt for the repair of the product or the replacement of faulty or defective parts with new parts, or with used parts of equivalent quality to new parts with regard to function and performance.
  • Page 3: Table Of Contents

    11.6. PARALLEL CONFIGURATION SPECIAL FEATURES ......47 Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 4: Safety Standards

    For such uses we would advise you to contact SOCOMEC beforehand to confirm the ability of these products to meet the required level of safety, performance, reliability and compliance with applicable laws, regulations and specifications.
  • Page 5: Description Of The Symbols Used On Labels Attached To The Unit

    READ THE USER MANUAL BEFORE USING THE UNIT We advise you to contact SOCOMEC beforehand to confirm the ability of these products to meet the required level of safety, perfor- mance, reliability and compliance with applicable laws, regulations and specifications.
  • Page 6: Installation Of The Unit

    • A space of at least 80 cm must be left above the UPS (see figure 2.2-3) for maintenance purposes. 2.2-1 2.2-2 2.2-3 ≥ 80 cm BATTERY BATTERY BATTERY CABINET CABINET CABINET 130° 130° door door free area free area Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 7: Internal Front View

    Power connections (behind the plastic protection) Input breaker (MAINS SUPPLY) Output breaker (emergency shutdown ESD) Aux mains breaker Manual maintenance bypass Handle interlocking (position 0) Cable ties Locking cable clamp (not provided) Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 8: Electrical Diagram

    2.4. ELECTRICAL DIAGRAM The following is a simple electrical diagram of the UPS unit. For connections details see chapter 3. 2.4-1 Electrical diagram BATTERY INPUT MAINS AUXILIARY MAINS MAINS UPS OUTPUT OPTIONS SOCKET Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 9: Electrical Requirements

    We suggest 35 mm for GP80 and 25 mm for the Green Power 2.0 using the protective devices in the above table. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 10: Backfeed Protection

    2 A time delay COM1 BKF MAIN 230 V 2 A time delay (1) COM1 and COM2 are connected to the neutral. Refer to the following paragraph for details on electrical connection. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 11: Connecting The External Backfeed Protection

    Separate Mains Distribution panel MAINS Trip coil Mains terminal block Aux Mains terminal block Mains switch Aux Mains switch Aux Mains BKF connector Mains BKF connector AUX MAINS See also section 3.1 Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 12 Mains BKF connector COMMON MAINS See also section 3.2 Remote switches - rated current Model 60 3/3 125 A AC1 125 A AC1 80 3/3 160 A AC1 160 A AC1 Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 13: Connections

    (see sec. 2.5 ) Cable specifications: • strip length: 18 mm • tightening torque: 3.5 - 4.5 Nm For systems installed on raised fl oors 20 cm A. Power cables 90° B. Control cables Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 14: Mains And Aux Mains Connected Separately

    L12 L22 L32 N2 MAINS LOAD MAINS 3.2. MAINS AND AUX MAINS CONNECTED TOGETHER 3.2-1 -B2 -B1 L2 L3 N L11 L21 L31 L12 L22 L32 N2 Max 50 mm (flexible) MAINS LOAD Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 15: External Battery Cabinet Connection

    • Reassemble the plastic terminal block protection. If using cabinets not supplied by SOCOMEC, it is the installer’s responsibility to check electrical compatibility and the presence of appropriate protective devices between the UPS and the battery cabinet (fuses and switches of sufficient capacity to protect the cables from the UPS to the battery cabinet).
  • Page 16: Modes Of Operation

    To activate ECO MODE go to MAIN MENU > COMMANDS > ECO MODE and select ACTIVATE ECO MODE. To disable ECO MODE, select RETURN TO NORMAL MODE. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 17: Operation In Converter Mode

    With a generator, the frequency and voltage ranges of the auxiliary mains can be increased to accept the instability of the GE and at the same time to avoid operation from the battery or risks of out-of-synchronisation switching on to the bypass. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 18: Human Machine Interface

    - Yellow: UPS on battery or the UPS points out a particular working mode - Flashing green: battery test is in progress - Green: the load is supplied - Off : inactive UPS Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 19: Mimic Panel Overview

    It must be formatted with FAT32 fi lesystem. Network icon: Displayed if a valid link has been established on the ethernet. Flashes when a remote host is communicating with the UPS. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 20 5. Unit output. 6. Output from static switch 7. Bypass input. Bar colour identify the energy fl ow: • blue: active/mains present • grey: mains not present 5.2-6 Load level Yellow Green Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 21 If there is a pending battery charger alarm the border turns yellow 5.2-8 Message area Message area Always present, displays a help message to guide the user through the display functions. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 22: Menu Navigation

    From the mimic panel page, press the ENTER key to access the MAIN MENU. Use the UP/DOWN key to scroll menu items, ENTER to confirm a choice, ESC to exit the current page or to abort an operation. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 23 5. HUMAN MACHINE INTERFACE Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 24 • CONNECTIVITY: configurations of communication options; • SLOT OPTIONS: configurations of available optional boards, which can be mounted on the front slots. System critical parameters are password protected and should be modified by specialist personnel only. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 25: Service Menu

    The Commissioning Code is provided directly by the relevant Support Centre upon communication of the serial number. When the Support Centre is contacted for the Commissioning Code, detailed information can be obtained on the UPS functions available and on scheduled preventive maintenance programmes. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 26 5.3.10. LANGUAGE UPGRADE Text translations in several languages are held in files with the *.lng extension which are provided by SOCOMEC. Language upgrades must be performed through the USB port, using a standard USB memory stick. The USB device must be formatted with FAT32 file system.
  • Page 27 BATTERY TEMPERATURE PROBE HISTORY LOG EVENT LIST STATISTICS COUNTERS SERVICE UPS REFERENCE FIRMWARE VERSION COMMISSIONING CODE SERVICE CODE UPGRADE FIRMWARE UPGRADE HMI FIRMWARE UPGRADE LANGUAGES UPGRADE WEB SERVER REPORT ON USB Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 28: Operating Procedures

    • configuration setting • UPS startup • battery circuit and automatic bypass testing The Commissioning Code is requested at the Commissioning Wizard startup (see chapter 5.3.9). Contact the support service for further information. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 29: Shutdown

    6. OPERATING PROCEDURES 6.3. SHUTDOWN Shutdown interrupts the power supply to the load and causes the UPS and battery charger to stop. • Enter menu MAIN MENU > COMMANDS > UPS PROCEDURES • Select Automatic Stop Procedure and press ENTER •...
  • Page 30: Emergency Shutdown

    6.8. UPS GENERAL POWER OFF Using a button/switch connected to the ADC (Advanced Dry Contacts) card it is possible to interrupt the continuous power provided by the UPS (see chapter 7.3). Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 31: Connectivity And Communication Options

    4 Data + for RS485 4 Reserved 5 GND 5 GND 6 Data − for RS485 6 Not connected 7 Reserved 7 RTS 8 Not connected 8 CTS 9 +12 V 9 +12 V Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 32: Standard Web

    The login is admin and the default password is public (lower case only). The password can be changed in the SETTINGS > PASSWORD web pages or on the HMI menu: MAIN MENU > SETTINGS > PREFERENCES > PASSWORDS > WEB PASSWORD. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 33 In the case of a parallel system, a line is added at the bottom of the display showing the current status of each unit. 7.2.3. Network configuration It is possible to configure the main network parameters using the SETTINGS > NETWORK web page. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 34 All active events are listed in the e-mail body. If the event has been cancelled by the UPS a cancelled event e-mail is also sent. It is possible to send a test e-mail. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 35: Adc Card

    (1) If the external ESD button is not used always insert a jumper to short circuit input IN 1. (2) The IN3 input on the ADC card with temperature sensor is for the external battery temperature sensor. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 36: Adc Card With Temperature Sensor

    A large number of SW solutions can be adopted on Green Power 2.0 thanks to its advanced communication facilities. These solu- tions have been specially designed for the efficient management of power protection devices. Visit www.socomec.com and click on DOWNLOAD then SOFTWARE to find the communication software suitable for your requirements.
  • Page 37: Electrical Options

    UPS. In this case the UPS can be turned off and removed without power interruption at the connected loads. For further information contact SOCOMEC. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 38: Troubleshooting

    The phase cycle sequence is incorrect. In this case, invert two phases of the input mains. For a UPS with separate auxiliary mains, exchange the two phases of the auxiliary mains only. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 39: Ups Alarms

    Battery switch open. • A60: FAN FAILURE Fault in the ventilation system. Check that the air inlet at the front and the air outlet at the back of the UPS are not obstructed. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 40: Preventive Maintenance

    It is strongly advisable to comply with any requests for preventive maintenance automatically displayed with an alert message All operations on equipment must only be carried out by SOCOMEC personnel or authorised support personnel. Maintenance consists of accurate functional checks on electronic and mechanical parts with replacement of parts subject to wear if necessary (typically batteries, fans and capacitors).
  • Page 41: Technical Specification

    1. 360 V with Pout = 90% Pn. 2. Initial Condition Pout ≤ 80% Pn 3. Pout ≥ 50% Sn. 4. @ Battery Fully Discharged. Call SOCOMEC support service. 5. @ Battery Fully Charged. Call SOCOMEC support service. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 43 Green Power 2.0 P a r a l l e l C o n f i g u r a t i o n...
  • Page 44: Ups Parallel Configuration

    (see at cheapter 2.5). Before turning on an individual UPS ensure that the relevant output switch E is closed. Before opening output switch E ensure that the relevant UPS is turned off. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 45 General differential magneto thermal switch (1). To avoid unwanted tripping, do not use the magneto-thermal switch. n * 0.5 A Differential input current: where n is the number of UPSs in parallel. Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 46: Parallel Setup Rules

    Parallel configuration must only be activated by SOCOMEC qualified personnel; in each case arrange the control cables in the relevant cable run as shown in figure 11.5-1, leaving the connector(s) unconnected (in the central UPS one incoming and one outgoing control cable must be used).
  • Page 47: Parallel Configuration Special Features

    UPS #1 in this example). The BATTERY SETTINGS menu and the AUTOMATIC STOP PROCEDURE are only available on this UNIT MENU. 11.6.2- 2 System view SYSTEM mimic panel is selected The SYS icon is selected Green Power 2.0 60-80 kVA - Ref.: IOMMASGPXX06-EN 06...
  • Page 48 11. UPS PARALLEL CONFIGURATION 11.6.3. Sequential start (confi gurable by Socomec service personnel only) In a parallel configuration a sequential start can be set in all the units. It allows a reduction of the power impact on the mains or GenSet when the UPS system resumes from battery mode.
  • Page 52 Fax. +48 22 825 73 60 info.ups.pl@socomec.com HEAD OFFICE YOUR DISTRIBUTOR SOCOMEC GROUP S.A. SOCOMEC capital 10 816 800€ *IOMMASGPXX06-EN 06* R.C.S. Strasbourg B 548 500 149 B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex - FRANCE Tel. +33 3 88 57 41 41 IOMMASGPXX06-EN 12.2016...