Fisher 4195 KB Series Instruction Manual page 4

Gauge pressure controllers
Table of Contents

Advertisement

4195KA, KB, and KC Series
Available Configurations
See table 1–2
Input Signal (Process Sensor Range)
Lower and Upper Range Limits: See tables 1–3
and 1–4
Maximum Allowable Operating Limits: See
tables 1–3 and 1–4
(1)
Output Signal
Proportional-Only, Proportional-Plus-Reset, or
Proportional-Plus-Reset-Plus-Rate Range: 3 to
15 psig or 6 to 30 psig (0.2 to 1.0 bar or 0.4 to 2.0
bar)
Action: Field-reversible between direct(increasing
sensed process pressure increases output pres-
sure) or reverse(increasing sensed process pres-
sure decreases output pressure).
Process Scale
Standard scale is matched to the range of the sens-
ing element, with the exception of receiver control-
(2)
lers. Optional
scales are available.
Process Connections
Standard: 1/4-inch NPT, female, stainless steel (all
input ranges)
Optional: 1/2-inch NPT. See table 1–5.
Supply and Output Connections
1/4-inch NPT, female
Supply Pressure Requirements
See table 1–6.
Remote Set Point Pressure Ranges
3 to 15 psig or 6 to 30 psig (0.2 to 1.0 bar or 0.4 to
2.0 bar)
Controller Adjustments
(1)
Proportional Band
span
1. These terms are defined in ISA Standard S51.1-1979.
2. Consult your Fisher sales office or sales representative for additional information.
3. Scfh—Standard cubic feet per hour (60 F and 14.7 psia). Normal m
4. Without auto/manual station. With auto/manual station, air consumption is 10.0 Scfh (0.28 normal m
1–4
Table 1–1. Specifications
(1)
: 5 to 500% of process input
3
/hr—Normal cubic meters per hour (0 C and 1.01325 bar, absolute).
(1)
Reset
: Adjustable from 0.01 to more than 74 min-
utes per repeat (from 100 to less than 0.0135 re-
peats per minute)
(1)
Rate
: Adjustable from 0 to 20 minutes
Set Point: Adjustable from 0 to 100% of the scale
span
Controller Performance
(1)
Repeatability
: 0.4% of output span
(1)
Dead Band
: Less than 0.4% of process scale
span
Typical Frequency Response: 1.5 hertz and 90
degree phase shift with 10 feet (3.05 m) of 1/4-inch
(6.4 mm) tubing and 100 cubic inch (1639 cm
ume
Steady-State Air Consumption
3 to 15 Psig (0.2 to 1.0 Bar) Output: 3.5 scfh (0.1
3
m
/hr)
6 to 30 Psig (0.4 to 2.0 Bar) Output: 5.0 scfh (0.14
3
m
/hr)
(3)
Delivery Capacity
3 to 15 Psig (0.2 to 1.0 Bar) Output: 240 scfh (5.9
3
m
/hr)
6 to 30 Psig (0.4 to 2.0 Bar) Output: 350 scfh (10.4
3
m
/hr)
(3)
Exhaust Capacity
3 to 15 Psig (0.2 to 1.0 Bar) Output: 186 scfh (4.6
3
m
/hr)
6 to 30 Psig (0.4 to 2.0 Bar) Output: 295 scfh (7.0
3
m
/hr)
Operative Ambient Temperature Limits
–40 to 160 F (–40 to 71 C)
Mounting
Controller can be mounted on actuator, panel, wall,
or pipestand.
Approximate Weight
10 pounds (4.5 kg)
3
/hr for either output range.
3
) vol-
(1,3,4)
(1)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4195 kc series4195 ka series