Diagnostic messages

A.1

Diagnostics messages and maintenance events

Diagnostic messages
For each diagnostic event, a diagnostic message is output and the ER LED flashes on the
module.
The diagnostic messages can, for example, be read from the diagnostic buffer of the CPU.
There can be more than one diagnostics alarm at the same time.
Table A-1
Diagnostic messages, their meaning and possible remedies
Diagnostics message Channel
error type
(CET)
Configuration error:
0x0602
Station Stop – No
server module
Configuration error:
0x0602
Station Stop – Mod‐
ule parameter <po‐
tential group> errors
or incorrect terminal
block present in real
slot <slot>
Configuration error:
0x0602
Permissible back‐
plane bus size excee‐
ded
Configuration error:
0x0602
Incorrect backplane
bus configuration in
slot <slot>
Configuration error:
0x0602
Impermissible bus
adapter on interface
module
Configuration error:
0x0602
No server module
Interface Module IM 155-6 PN HA (6DL1155-6AU00-0PM0)
Manual, 05/2017, A5E39262148-AA
Extended
Assignment
channel
error type
(CET)
0x0693
Configura‐
tion
0x0691
Configura‐
tion
0x0698
Configura‐
tion
0x0699
Configura‐
tion
0x069C
Configura‐
tion
0x069E
Configura‐
tion
Meaning
No server module was present
during power-up of an
ET 200SP HA station.
The installed terminal block
does not match the configura‐
tion.
The total width of the installed
modules exceeds the permissi‐
ble assembly length of
1300 mm.
The maximum current demand
of all plugged-in modules ex‐
ceeds 2100 mA.
The accompanying <slot> val‐
ue indicates the slot causing
the error.
The installed bus adapter does
not match the configuration.
The server module is pulled
during operation of an
ET 200SP HA station.
A
Remedy
Verify that the server mod‐
ule is correctly installed in
the rack.
Ensure that a matching ter‐
minal block is installed.
Verify that the backplane
bus configuration does not
exceed the permissible size.
The server module must be
the last module plugged in
(highest permissible slot
number: 58).
Check the configuration of
the ET 200SP HA.
Verify that a matching bus
adapter is installed.
Ensure that the server mod‐
ule is correctly installed in
the rack.
31