Product overview
2.1 Properties
The interface has the following technical properties:
● Supply voltage 1L+ 24 V DC (SELV/PELV).
The supply voltage is fed via the carrier module.
The connection plug is included in the scope of delivery of the interface module.
● PROFINET IO connection via BusAdapter (see following paragraph, "Accessories")
The interface supports the following functions:
● Firmware update
● I&M identification data
● Pulling and plugging modules in RUN
● Value status QI
● IO redundancy
● Time stamping
● Multi Hot Swap (pulling/plugging of multiple I/O modules during operation)
● Saving service data
● Recording the value status of I/O modules
● Reference temperature distribution
You can configure the interface with HW Config and integrate it into your system
Note
The IM 155‑6 PN HA cannot be pulled/plugged when the associated connector for the supply
voltage is plugged in.
PROFINET IO functions
The interface supports the following PROFINET IO functions:
● Integrated BusAdapter with 2 ports
● Supported Ethernet services: ping, arp, network diagnostics (SNMP)/MIB-2, LLDP-MIB and
MRP-MIB
● Port diagnostics
● Disabling of ports
● Minimum update time of 250 µs
● Device replacement without programming device (PG)
● Reset to factory settings via PROFINET IO
● System redundancy S2
● System redundancy R1
● Media redundancy (MRP)
● Support of submodules on suitable I/O modules
8
Interface Module IM 155-6 PN HA (6DL1155-6AU00-0PM0)
Manual, 05/2017, A5E39262148-AA