Diagnostic messages
A.1 Diagnostics messages and maintenance events
Diagnostics message Channel
error type
(CET)
Redundancy error:
0x0630
Failure in the partner
module <internal er‐
ror code>
Redundancy error:
0x0630
Faulty power supply
Redundancy error:
0x0630
Incorrect bus adapter
in partner module
Maintenance events
A maintenance event is generated each time a maintenance requirement is identified. The MT
LED lights up on the module.
Maintenance messages do not directly affect the function of the module.
Table A-2
Maintenance messages, their meaning and possible remedies
Maintenance mes‐
Channel
sage
error type
(CET)
Error in the retentive
0x0640
memory of the inter‐
face module
Error in the retentive
0x0640
memory of the BusA‐
dapter
PROFINET IO
Another source of diagnostic events is the PROFINET basic technology in use. It generates
diagnostics messages containing coding that is already defined in the PROFINET IO Standard
- Application Layer Service Definition V2.2.
The actual diagnostics scope used depends on the configuration and parameter assignment.
You can download the standard as needed on the Internet (http://www.profibus.com) from the
home page of the PROFIBUSuser organization.
32
Extended
Assignment
channel
error type
(CET)
0x06D0
Redundant
modules
0x06D1
Redundant
modules
0x06D2
Redundant
modules
Extended
Assignment
channel
error type
(CET)
0x06E0
Module
0x06E1
Module
Meaning
Errors in the redundancy of the
interface module are signaled.
The accompanying <internal
error code> value provides in‐
formation for service experts.
Problems with the power sup‐
ply.
The bus adapter of the redun‐
dancy partner module is not
present or is not supported.
Meaning / Cause
Fault detected in the data
block on the mounting module
during operation
A memory block error on the
bus adapter was detected dur‐
ing operation.
Interface Module IM 155-6 PN HA (6DL1155-6AU00-0PM0)
Remedy
Replace the partner inter‐
face module.
Check the power supply for
possible errors, e.g. over‐
load, short-circuit.
Replace the interface mod‐
ule, if necessary/
Replace the bus adapter in
the partner module.
Remedy
Replace carrier module
Replace the bus adapter.