Power management
Automatic gen-set start / stop function based on load changes and/or Running hours or Generator size.
Following functions are available:
Power management in kW
Guarantees adjustable load reserve (load step) in kW. Suitable for load demand-based optimization.
Activation: #Pwr mgmt mode = ABS (kW)
Power management in kVA
Guarantees adjustable load reserve (load step) in kVA. Suitable for generator- or busbar dimensioning-
based optimization.
Activation: #Pwr mgmt mode = ABS (kVA)
Relative power management in %
Guarantees that the engines will be not continuously loaded more than to a certain level, leaving less than
selected relative load reserve. Suitable for engine life-based optimization.
Activation: #Pwr mgmt mode = REL (%)