Internal device error 1
Parameter info
75
76
No emergency mode
77
Program loading error
Additional message at the fault
alarm contact!
78
Options parameter
Diagnostic alarms
79
80
Diagnostic parameters
81
Reference graphs
Internal device error
Remedy Return the positioner to SAMSON AG for repair.
Error in the parameter info which is not critical for the control.
Remedy Confirm error.
Check and, if necessary, reset required parameters.
The travel measuring system of the positioner has a self-moni-
toring function (see Code 62).
A controlled emergency mode is not available on certain actua-
tors, such as double-acting actuators. For this reason, the
positioner moves into the fail-safe position when a measuring
error occurs. During the initialization, the positioner checks
whether the actuator has such a function or not.
Remedy Merely information, confirm, if necessary.
No further action necessary.
When the device starts operation for the first time after the input
signal has been applied, it carries out a self-test ( tEStinG runs
across the display).
If the device loads a program that does not correspond to that of
the positioner, the valve is moved into the fail-safe position. It is
not possible to make the valve leave this fail-safe position again
by operating the positioner.
Remedy Interrupt current supply and restart positioner. Otherwise, return
the positioner to SAMSON AG for repair.
Errors in options parameters, e.g. due to EMC disturbances.
Remedy Return the positioner to SAMSON AG for repair.
Alarms are generated in the EXPERT
+
EXPERT
has been successfully activated in Code 48.
Error which is not critical for control.
Remedy Confirm error.
Check and, if necessary, start new reference run.
Error on plotting the reference graphs of drive signal Y stationary
or drive signal Y hysteresis.
• Reference run was interrupted
• Reference line Y stationary or Y hysteresis was not adopted.
Code list
+
extended diagnostics if
EB 8384-2 EN
79