UMG 511
Voltage measurement
The voltage measuring inputs are suitable for the following grids of power supply:
Three-phase 4 conductor systems with nominal voltages till
Three-phase 3 conductor systems with nominal voltages till
The voltage measuring inputs regarding safety and reliability reasons are dimensioned as follows:
Overvoltage category
Measurement surge voltage
Measuring range L-N
Measuring range L-L
Resolution
Crest factor
Impedance
Power consumption
Scanning frequency
Transients
2)
U
acording to EN61000-4-30
din
Flicker range (dU/U)
Frequency of fundamental oscillation
-
Resolution
1)
The UMG511 can only ascertain measurement values when a measurement voltage higher than 10Veff L-N or
18Veff L-L is applied to at least one voltage measurement input
2)
U
= agreed input voltage according to DIN EN 61000-4-30
din
90
417V/720V (+10%)
600V (+10%)
600V CAT III
6kV
1)
0
.. 600V
rms
1)
0
.. 1000V
rms
0.01V
1,6 (relating to 600V
)
rms
4MOhm/phase
ca. 0.1VA
20kHz/phase
50µs
100 .. 250V
27.5%
15Hz .. 440Hz
0.001Hz