Parameter data record

A.1

Dependencies when configuring with GSD file

When configuring the module with a GSD file, remember that the settings of some
parameters are dependent on each other.
Configuring with a PROFINET GSD file
The table lists the properties and their dependencies on the measurement type and
measuring range for PROFINET.
Measurement type
Measuring
range
Deactivated
Current
0 mA to
(4-wire transducer)
20 mA
4 mA to
20 mA
±20 mA
Current
0 mA to
(2-wire transducer)
20 mA
4 mA to
20 mA
x = Property is allowed, - = Property is not allowed, * = Property is not relevant
Configuring with a PROFIBUS GSD file
The table lists the properties and their dependencies on the measurement type and
measuring range for PROFIBUS.
Measurement type
Measuring
range
Deactivated
Current
0 mA to 20 mA
(4-wire transducer)
4 mA to 20 mA
+/- 20 mA
Current
0 mA to 20 mA
(2-wire transducer)
4 mA to 20 mA
x = Property is allowed, - = Property is not allowed, * = Property is not relevant
28
No supply volt-
Short-circuit to
age L+
ground
*
*
x
x
x
x
x
x
x
x
x
x
No supply voltage
L+
*
x
x
x
x
x
Diagnostics
Overflow
*
x
x
x
x
x
Diagnostics
Short-circuit to
Overflow/underflow Wire break
ground
*
*
x
x
x
x
x
x
x
x
x
x
Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1)
A
Underflow
Wire break
*
*
x
-
x
x
x
-
-
-
x
x
*
-
x
-
-
x
Manual, 12/2015, A5E36104399-AA