Parameters/address space
4.1
Parameters
DQ 8x24VDC/0,5A SNK BA parameters
Specify the module properties with the various parameters in the course of your STEP 7
configuration. The following table lists the configurable parameters. The effective range of
the configurable parameters depends on the type of configuration.
The following configurations are possible:
● Central operation with an ET 200SP CPU
● Distributed operation on PROFINET IO in an ET 200SP system
● Distributed operation with PROFIBUS DP in an ET 200SP system
When assigning parameters in the user program, use the "WRREC" instruction to transfer
the parameters to the module by means of data records (see chapter Parameter assignment
and structure of the parameter data record (Page 25)).
Table 4- 1
Configurable parameters and their defaults (GSD file)
Parameter
Diagnostics
Disable
•
No supply
Enable
•
voltage L+
Channel
Disable
•
activated
Enable
•
Reaction to
Turn off
•
CPU STOP
Keep last value
•
Output substitute value 1
•
Potential
Use potential group of the
•
group
left module (module
plugged into a dark-colored
BaseUnit)
Enable new potential group
•
(module plugged into light-
colored BaseUnit)
Only when configuring using a PROFIBUS GSD file; does not apply to configuration with STEP 7 via HSP. The parame-
1
ter assignment options are limited because PROFIBUS GSD configuration limits the number of parameters to a maxi-
mum of 244 bytes for each ET 200SP station. If required, you can still assign these parameters using the data record
128 as described in the column "GSD file PROFINET IO" (see table above). The parameter length of the I/O module is
16 bytes.
Digital output module DQ 8x24VDC/0.5A SNK BA (6ES7132-6BF61-0AA0)
Manual, 09/2017, A5E32855878-AB
Value range
Disable
Enable
Turn off
Use potential
group of the left
module
Default
Reconfiguration
in RUN
Yes
Yes
Yes
No
Scope with configuration software,
e.g. STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Module
Module
Channel
Channel
Channel
Module
Module
Module
4
1
15