Article number
Switching frequency
with resistive load, max.
•
with inductive load, max.
•
on lamp load, max.
•
Total current of the outputs
Current per channel, max.
•
Current per module, max.
•
Total current of the outputs (per module)
horizontal installation
–
up to 60 °C, max.
vertical installation
–
up to 50 °C, max.
Cable length
shielded, max.
•
unshielded, max.
•
Isochronous mode
Isochronous operation (application synchro-
nized up to terminal)
Interrupts/diagnostics/status information
Diagnostics function
Substitute values connectable
Alarms
Diagnostic alarm
•
Diagnostic messages
Monitoring the supply voltage
•
Wire-break
•
Short-circuit
•
Diagnostics indication LED
Monitoring of the supply voltage (PWR-
•
LED)
Channel status display
•
for channel diagnostics
•
for module diagnostics
•
Potential separation
Potential separation channels
between the channels
•
between the channels and backplane bus
•
Digital output module DQ 8x24VDC/0.5A SNK BA (6ES7132-6BF61-0AA0)
Manual, 09/2017, A5E32855878-AB
6ES7132-6BF61-0AA0
100 Hz
0.5 Hz
10 Hz
0.5 A
4 A
4 A
4 A; in all other mounting positions
1 000 m
600 m
No
Yes
Yes
Yes
Yes
No
No
Yes; green PWR LED
Yes; Green LED
No
Yes; green/red DIAG LED
No
Yes
Technical specifications
6.1 Technical specifications
23