Connecting To The Power Supply Module - Mitsubishi MELSEC User Manual

Safety programmable controller
Table of Contents

Advertisement

10
LOADING AND INSTALLATION

10.3.2 Connecting to the power supply module

The following figure shows the wiring example of power lines, grounding lines, etc. to the
unit.
10
- 22
10.3 Wiring
10.3.2 Connecting to the power supply module
100/110VAC
AC
Fuse
AC
DC
24VDC
Connect to 24VDC
terminals of module
that requires 24VDC
internally.
* 1: The ERR. terminal turns ON/OFF as described below.
The terminal turns OFF (opens) when the AC power is not input, a CPU module stop error
(including a reset) occurs, or the fuse of the power supply module is blown.
POINT
1. Use the thickest possible (max. 2 mm
and 24 VDC power cables. Be sure to twist these wires starting at the connec-
tion terminals. For wiring a terminal block, be sure to use a solderless termi-
nal. To prevent short-circuit due to loosening screws, use the solderless
terminals with insulation sleeves of 0.8 mm (0.03 inch) or less thick. The num-
ber of the solderless terminals to be connected for one terminal block are lim-
ited to 2.
2.The ERR. terminal can not be used as a safety output. In addition, set the cable
for ERR. contact in the control panel and its length to 30m (98.43 ft.) or less.
Main base unit
(QS034B)
CPU module
QS061P-A1
Ground wire
Grounding
Figure 10.24 Wiring example
2
(14 AWG)) wires for the 100/200 VAC
Solderless terminals
with insulation sleeves
ERR 1
FG
LG
INPUT
100-120VAC
Terminal block