Component Identification - M-system R3-ND1 Instruction Manual

Devicenet interface module

Advertisement

COMPONENT IDENTIFICATION

FRONT VIEW
DR1
DR0
NA5
MS Indicator LED
NA4
NA3
NA2
NA1
NA0
NS Indicator LED
Configuration Jack
Euro Type
Connector Terminal
4
5
6
■ NODE ADDRESS & BAUD RATE DIP SW
• Node Address: 1 – 6 (NA0 – NA5)
1 (NA0)
2 (NA1)
3 (NA2)
2
2
2
0
1
2
A node address is defined in 6-digit binary code. 1 – 6 (NA0
to NA5) correspond to the least to most significant digits.
DIP SW
6
5
4
3
NA5
NA4
NA3
NA2
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
:
:
:
:
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
• Baud Rate: 7, 8 (DR0, DR1)
BAUD RATE
125 kbps
250 kbps
500 kbps
N/A
(*) Factory setting
■ INDICATORS
The following table defines the LED states of the MS, and
NS indicators.
LED
STATE
Green
Operating in a normal condition
Flashing Green
Standby (needs commissioning)
MS
Red
Critical failure
Flashing Red
Minor failure
OFF
No power supplied
Green
Link on-line and connections in the
established state
Flashing Green
Link on-line but no connections in
the established state
NS
Red
Critical link failure
Flashing Red
Minor link failure
OFF
No power supplied
Node Address & Baud Rate
8
Baud Rate
7
Setting
6
5
Node
4
Address
3
Setting
2
1
ON
1
2
3
4 (NA3)
5 (NA4)
6 (NA5)
2
2
2
3
4
NODE
2
1
ADDRESS
NA1
NA0
0
0
0
0
1
1
1
0
2
1
1
3
:
:
:
0
0
60
0
1
61
1
0
62
1
1
63
0 = OFF, 1 = ON
7 (DR0)
8 (DR1)
OFF (*)
OFF (*)
ON
OFF
OFF
ON
ON
ON
TO INDICATE
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81 ( 6 ) 6659-8201 Fax: +81 ( 6 ) 6659-8510 E-mail: info@m-system.co.jp
SIDE VIEW
■ SIDE DIP SW
(*) Factory setting
• Data Allocation: SW1, SW2
5
Data Allocation Type* must be assigned to each I/O module
position to specify how many data areas (four types) are to
be occupied by each.
Two bits from SW1 and SW2 are assigned to each posi-
tion, and data areas can be specified from the module No. 1
through 8. Setting for No. 9 and later modules is identical
to No. 8.
SW ASSIGNMENT
SW1-1
SW1-3
SW1-5
SW1-7
SW2-1
SW2-3
SW2-5
SW2-7
SW SETTTING
OFF
ON
OFF
ON
* Refer to the specifications of the related series for the Data
Allocation Type of I/O modules.
• Dual Communication: SW3-1
When two network modules are mounted, one must be
'Main' (OFF) network and the other must be 'Sub' (ON)
network. For single communication, the network module
must always be set to 'Main' (OFF).
SW
SW3-1
• Input Error Data: SW3-2
Hold: When the communication from an input module is lost
due to the input module error, the network module holds the
signal and stands by until the communication recovers.
Set to '0': When the communication from an input module
is lost due to the input module error, the network module
outputs '0.'
SW
SW3-2
Note: Be sure to set unused SW3-3 and 3-4 to OFF.
DIP SW
SW3
SW2
4
8
3
7
2
6
1
5
4
ON
3
2
1
ON
MODULE NO.
SW1-2
SW1-4
SW1-6
SW1-8
SW2-2
SW2-4
SW2-6
SW2-8
DATA ALLOCATION
OFF
OFF
ON
ON
DUAL COMMUNICATION
MAIN (*)
OFF
INPUT ERROR DATA
HOLD (*)
SET '0'
OFF
EM-8353 Rev.11 P. 2 / 6
R3-ND1
SW1
8
7
6
5
4
3
2
1
ON
1
2
3
4
5
6
7
8
1
4
8
16
SUB
ON
ON