MODULE STATUS, ERROR STATUS, DATA ERROR STATUS
Shows each module's availability and error status.
15
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ ANALOG DATA (models: R3-SV4, YV4, DS4, YS4 and US4, etc.)
16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary). Negative percentage is represented in 2's
complements.
15
■ TEMPERATURE DATA (models: R3-RS4, TS4 and US4, etc.)
16-bit binary data.
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data. For example, 135.4°F is con-
verted into 135.
Minus temperature is converted into negative values, represented in 2's complements.
15
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
32-bit binary data is used for accumulated counts and encoder positions.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
15
+0
15
+1
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
32-bit binary data is used for BCD.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.
15
+0
15
+1
■ DISCRETE DATA (models: R3-DA16 and DC16, etc.)
15
0 : OFF
1 : ON
0
Module 1
Module 2
Module 3
:
Module 16
0
0
0
Lower 16 bits
0
Higher 16 bits
0
Lower 16 bits
0
Higher 16 bits
0
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
:
:
Input 16 (Output 16)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81 ( 6 ) 6659-8201 Fax: +81 ( 6 ) 6659-8510 E-mail: info@m-system.co.jp
R3-ND1
EM-8353 Rev.11 P. 5 / 6