Dimensions and Weights
Table 2.
Performance air handler model UCCA data
1500
Nom airflow (CFM)
Unit size
3
Fan/Motor data
FC fans
Wheel size (in.)
9x7
Maximum RPM
2000
Motor HP
1-2
Minimum design CFM
1050
DDP fans
Wheel size (in.)
11
Maximum RPM
3600
Motor HP
1-2
Filters (height x width - inches) with quantity per size
2 in. and 2/4 in. combination flat filter
- 16 x 20
- 16 x 25
- 20 x 20
- 20 x 25
1
2
Area (ft
)
3.5
Nominal Velocity (fpm)
432.0
2-in. Angle Filter
- 16 x 20
- 16 x 25
2
- 20 x 20
- 20 x 25
2
Area (ft
)
5.6
Nominal Velocity (fpm)
270.0
Mix Box
2
Damper Area (ft
)
1.3
Nominal Velocity (fpm)
1166.9
Notes: Hydronic coil weight based on 14 fins per inch. Steam coil weight based on 6 fins per inch.
Coil width = length in direction of coil header, typically vertical.
Coil length = length of coil in direction of the coil tubes, typically horizontal and perpendicular to airflow.
Unit sizes 21-30 have two stacked steam coils
Fan wheel size is diameter x length of blade (width).
Minimum airflow limit is for units with hot water, steam, or electric heat. There is no minimum airflow for cooling-only units.
16
3000
4000
5000
6
8
10
12x9
12x12
15x15
1500
1700
1400
1-3
1-5
1 - 5
2100
2800
3500
14
16
18
3600
3400
3025
1 1/2 - 5
2- 7 1/2
3 - 7 1/2
4
4
2
6.9
8.9
11.1
432.0
450.0
450.0
2
4
2
4
2
11.1
12.5
15.6
270.0
320.0
321.4
2.4
3.1
4.1
1224.7
1288.5
1205.6
6000
7000
3500
12
14
7
18x15
18x18
20x15
1200
1200
1100
1 - 7 1/2
1 - 7 1/2
1 - 10
4200
4900
5950
18
20
20
3025
2720
2720
3 - 10
3 - 15
3 - 15
2
2
4
1
1
2
2
4
1
1
16.3
16.3
20.0
369.2
430.8
425.0
6
6
6
3
3
6
21.7
21.7
30.0
276.9
323.1
283.3
5.1
5.6
7.0
1178.0
1239.2
1217.0
10500
12500
15000
21
25
30
20x20
20x18
22x20
1000
1300
1150
2 - 15
3 - 15
1 1/2 - 15
7350
8750
10500
2 x 18
2 x 20
2 x 20
3025
2720
2720
3- 10
3- 10
5 - 15
2
2
2
6
2
2
6
4
22.5
26.4
30.6
466.7
473.7
490.9
4
12
8
8
12
31.1
41.7
48.9
337.5
300.0
306.8
8.2
10.3
12.0
1277.9
1208.1
1247.1
CLCH-SVX009A-EN