Trane TWE030CA Product Data

Trane TWE030CA Product Data

Heat pump split system air conditioning 30 to 50 mbh - 50 hz air handler models,condensing models

Advertisement

Insight
Ducted Air Handler

Product Data

Heat Pump Split System Air Conditioning
30 to 50 MBh - 50 Hz
Air Handler Models
TWE030CA
TWE040CA
TWE050CA
Condensing Models
TWJ020-036CA
TWA030-060CD
TWE-PRC001-EN-10-15-99

Advertisement

Table of Contents
loading

Summary of Contents for Trane TWE030CA

  • Page 1: Product Data

    ™ Insight Ducted Air Handler Product Data Heat Pump Split System Air Conditioning 30 to 50 MBh - 50 Hz Air Handler Models Condensing Models TWE030CA TWJ020-036CA TWE040CA TWA030-060CD TWE050CA TWE-PRC001-EN-10-15-99...
  • Page 2: Features And Benefits

    Condensing Units Features: Benefits: • Vertical Air Discharge • Flexibility in application ® • High Efficiency TRANE Climatuff • Quality and reliability Compressor • Uniform covering for a smooth, attractive • Powder Paint finish and corrosion-resistant finish • Brazed connections •...
  • Page 3: Table Of Contents

    Contents Features and Benefits Air Handling Units Condensing Units System Performance Selection Procedure Model Number Nomenclature General Data TWE030CA40B TWE040CA40C TWE050CA50D TWJ020CA00A0 TWJ024CA00A0 TWJ030CA00A0 TWJ036CA00A0 TWA030CD00A0 TWA040CD00A0 TWA050CD00A0 TWA060CD00A0 Performance Data TWJ/TWE Cooling TWA/TWE Cooling TWJ/TWE Heating TWA/TWE Heating Evaporator Fan Performance Air Pressure Drop Supplementary Heaters Electrical Data...
  • Page 4: System Performance

    System Performance Cooling Capacity 95° F (35° C) Outdoor Unit Indoor Unit Ducted Air Handlers TWJ020CA00A TWE030CA00A 1185 TWJ024CA00A TWE030CA00A 1520 TWJ030CA00A TWE030CA00A 1000 1690 TWJ030CA00A TWE040CA00A 1100 1860 TWJ036CA00A TWE030CA00A 1100 1860 TWJ036CA00A TWE040CA00A 1325 2240 40.5 11.5 TWJ036CA00A TWE050CA00A 1400 2360...
  • Page 5: General Data

    General Data TWE Product Specifications Model TWE030CA40B TWE040CA40C TWE050CA50D Power Conn.— Volts/Ph/Hz 220/1/50 220/1/50 220/1/50 Indoor Coil - Type Plate Fin Plate Fin Plate Fin Rows Fins per inch (Fins per 25.4 mm) Face Area sq ft (sq m) 3.21 (.30) 5.04 (.47) 6.19 (.58) Tube Size in.
  • Page 6: Twj020Ca00A0

    General Data TWJ Product Specifications Model TWJ020CA00A0 TWJ024CA00A0 TWJ030CA00A0 TWJ036CA00A0 200/230/1/60 200/230/1/60 200/230/1/60 200/230/1/60 Power Conn. - Volts/Ph/Hz Fuse Size - max. amps PER LOCAL CODES PER LOCAL CODES PER LOCAL CODES PER LOCAL CODES ® ® ® ® Compressor - Type CLIMATUFF CLIMATUFF CLIMATUFF...
  • Page 7: Twa030Cd00A0

    General Data TWA Product Specifications Model TWA030CD00A0 TWA040CD00A0 TWA050CD00A0 TWA060CD00A0 380/415/3/60 380/415/3/60 380/415/3/60 380/415/3/60 Power Conn. - Volts/Ph/Hz Fuse Size - max. amps PER LOCAL CODES PER LOCAL CODES PER LOCAL CODES PER LOCAL CODES ® ® ® ® Compressor - Type CLIMATUFF CLIMATUFF CLIMATUFF...
  • Page 8: Performance Data

    Performance Data Cooling English Units TWJ020CA WITH TWE030CA4 AT 700 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. CORRECTION FACTORS - OTHER AIRFLOWS D.B. W.B. CAP. (MULTIPLY OR ADD AS INDICATED) 18.2 15.5 16.7...
  • Page 9 Performance Data Cooling Metric Units TWJ020CA WITH TWE030CA4 AT 1189 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. CORRECTION FACTORS - OTHER AIRFLOWS D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 (MULTIPLY OR ADD AS INDICATED)
  • Page 10 Performance Data Cooling English Units TWJ030CA WITH TWE040CA4-B AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. CORRECTION FACTORS - OTHER AIRFLOWS D.B. W.B. CAP. (MULTIPLY OR ADD AS INDICATED) 30.7 25.1 27.1...
  • Page 11 Performance Data Cooling Metric Units TWJ030CA WITH TWE040CA4-B AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. CORRECTION FACTORS - OTHER AIRFLOWS D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 (MULTIPLY OR ADD AS INDICATED)
  • Page 12: Twa/Twe Cooling

    Performance Data Cooling English Units TWA030CD WITH TWE030CA4 AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. CORRECTION FACTORS - OTHER AIRFLOWS D.B. W.B. CAP. (MULTIPLY OR ADD AS INDICATED) 28.8 22.6 24.4...
  • Page 13 Performance Data Cooling Metric Units TWA030CD WITH TWE030CA4 AT 1698 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. CORRECTION FACTORS - OTHER AIRFLOWS D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 (MULTIPLY OR ADD AS INDICATED)
  • Page 14 Performance Data Cooling English Units TWA040CD WITH TWE050CA5-C AT 1500 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. CORRECTION FACTORS - OTHER AIRFLOWS D.B. W.B. CAP. (MULTIPLY OR ADD AS INDICATED) 40.1 33.2 35.9...
  • Page 15 Performance Data Cooling Metric Units TWA040CD WITH TWE050CA5-C AT 2547 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. CORRECTION FACTORS - OTHER AIRFLOWS D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 (MULTIPLY OR ADD AS INDICATED)
  • Page 16: Twj/Twe Heating

    Performance Data Heating English Units TWJ020CA WITH TWE030CA4 AT 700 CFM O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT CORRECTION FACTORS - OTHER AIRFLOWS TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP. (VALUE AT 700 CFM TIMES CORR. FACTOR = VALUE AT NEW AIRFLOW) 0.00 0.00...
  • Page 17 Performance Data Heating Metric Units TWJ020CA WITH TWE030CA4 AT 1189 CMH O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT CORRECTION FACTORS - OTHER AIRFLOWS TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP. (VALUE AT 1189 CMH TIMES CORR. FACTOR 15.6 21.1 23.9...
  • Page 18 Performance Data Heating English Units TWJ030CA WITH TWE040CA4-B AT 1100 CFM O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT CORRECTION FACTORS - OTHER AIRFLOWS TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP. (VALUE AT 1100 CFM TIMES CORR. FACTOR = VALUE AT NEW AIRFLOW) 0.00 0.00...
  • Page 19 Performance Data Heating Metric Units TWJ030CA WITH TWE040CA4-B AT 1868 CMH O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT CORRECTION FACTORS - OTHER AIRFLOWS TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP. (VALUE AT 1868 CMH TIMES CORR. FACTOR 15.6 21.1 23.9...
  • Page 20: Twa/Twe Heating

    Performance Data Heating English Units TWA030CD WITH TWE030CA4 AT 1000 CFM O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT CORRECTION FACTORS - OTHER AIRFLOWS TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP. (VALUE AT 1000 CFM TIMES CORR. FACTOR = VALUE AT NEW AIRFLOW) 7.48 7.28...
  • Page 21 Performance Data Heating Metric Units TWA030CD WITH TWE030CA4 AT 1698 CMH O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT CORRECTION FACTORS - OTHER AIRFLOWS TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP. (VALUE AT 1698 CMH TIMES CORR. FACTOR 15.6 21.1 23.9...
  • Page 22 Performance Data Heating English Units TWA040CD WITH TWE050CA5-C AT 1500 CFM O.D. HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT CORRECTION FACTORS - OTHER AIRFLOWS TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP. (VALUE AT 1500 CFM TIMES CORR. FACTOR = VALUE AT NEW AIRFLOW) 9.68 9.46...
  • Page 23 Performance Data Heating Metric Units TWA040CD WITH TWE050CA5-C AT 2547 CMH O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT CORRECTION FACTORS - OTHER AIRFLOWS TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP. (VALUE AT 2547 CMH TIMES CORR. FACTOR 15.6 21.1 23.9...
  • Page 24: Evaporator Fan Performance

    Performance Data Evaporator Fan Performance Blower Performance — TWE030CA40B — Wet Coil EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS) UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes) 220 VOLTS 220 VOLTS 1018.8 0.72 (179.4) 0.71 (176.9) 1103.7 0.62 (154.4) 0.61 (152.0) 1188.6...
  • Page 25 Performance Data Evaporator Fan Performance Blower Performance — TWE050CA50D — Wet Coil EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS) UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes) 220 VOLTS 220 VOLTS 1528.2 1613.1 0.63 (156.9) 1000 1698.0 0.61 (152.0) 0.62 (154.4) 1050...
  • Page 26: Air Pressure Drop

    Performance Data Air Pressure Drop (Inches) - Electric Heaters Pressure Drop For Electric Heaters In Air Handler Models NUMBER OF RACKS AIRFLOW AIRFLOW AIR PRESSURE DROP IN. W.G. (PASCALS) 1018.8 0.01 (2.5) 0.02 (5.0) 0.02 (5.0) 1188.6 0.01 (2.5) 0.02 (5.0) 0.02 (5.0)
  • Page 27: Supplementary Heaters

    Supplementary Heaters THESE AIR HANDLERS ARE CONVERTIBLE AND MOTOR SPEED TAPS VARY BY THE UNIT ORIENTATION. TWE030C-Heater Model Number BAY96X Unit 1405 1406 1408,F 1410,F 1410A 1411 1411A 1415 1419 1421 3411 3415 Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 8.8 KW...
  • Page 28: Electrical Data

    Electrical Data System Wiring Diagram Legend Symbols NOTES: 1. DO NOT USE REQ TRANSFORMER LEAD IN THIS APPLICATION 2. ACCESSORY KIT BAY24X038 MAY BE USED WHEN AUTOMATIC SPEED CHANGE FOR HEATING/COOLING OPERATION IS DESIRED. TWE5-PRC001-EN-10-15-99...
  • Page 29: Dimensions

    Dimensions TWE030-050C Outline Drawing ALL DIMENSIONS ARE IN INCHES (MM) MINIMUM UNIT CLEARANCE SALE FLOW MODEL NO. CONTROL TO COMBUSTIBLE SERVICE CLEARANCE TWE030CA4 43.00 15.57 21.50 19.50 20.28 21.63 FCCV MATERIAL (REQUIRED) (RECOMMENDED) (1092.2) (395.5) (761.1) (495.3) (515.1) (549.4) SIDES (50.8) TWE040CA4 51.75...
  • Page 30 Dimensions TWJ020-036CA and TWA030-060CA Outline Drawing All dimensions are in inches (mm) SERVICE PANEL ELECTRICAL AND REFRIGERANT COMPONENTS CLEARANCES PER PREVAILING TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST FIVE (5) FEET ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, (175) AND SHOULD BE AT LEAST 12"...
  • Page 31: Convertibility

    Convertibility TWE030 Through 050 Convertibility Six (6) Way Convertibility One Unit - 4 Applications Easy Conversion to Opposite Side Access TWE5-PRC001-EN-10-15-99...
  • Page 32: Mechanical Specification Options

    Trane International Unitary Systems Stocking Location P.I.-L 1789 Chaussée de Wavre 1160 Brussels Belgium www.trane.com Since The Trane Company has a policy of continuous product improvement, it reserves the right to change An American Standard Company design and specifications without notice.