Air Filters

WARNING
Rotating Components!
The following procedure involves working with rotating
components. Disconnect all electric power, including
remote disconnects before servicing. Follow proper
lockout/ tagout procedures to ensure the power can
not be inadvertently energized. Secure rotor to ensure
rotor cannot freewheel. Failure to secure rotor or
disconnect power before servicing could result in
rotating components cutting and slashing technician
which could result in death or serious injury.

Throwaway Filters

To replace throwaway filters, install new filters with the
directional arrows pointing in the direction of airflow.
Note: Bag and cartridge filters must have an airtight seal
to prevent air bypass. If using filters not supplied by
Trane, apply foam gasketing to the vertical edges of
the filter.

Coils

All coils should be kept clean to maintain maximum
performance.
Figure 47.
Gain access to both sides of coil shown for sizes 3, 6, 10, and 12
CLCH-SVX009A-EN

Steam and Water Coils

WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
WARNING
Hazardous Chemicals!
Coil cleaning agents can be either acidic or highly
alkaline and can burn severely if contact with skin
occurs. Handle chemical carefully and avoid contact
with skin. ALWAYS wear Personal Protective Equipment
(PPE) including goggles or face shield, chemical
resistant gloves, boots, apron or suit as required. For
personal safety refer to the cleaning agent
manufacturer's Materials Safety Data Sheet and follow
all recommended safe handling practices. Failure to
follow all safety instructions could result in death or
serious injury.
To clean steam and water coils:
1. Disconnect all electrical power to the unit.
2. Gain access to both sides of the coil. For DDP fans,
remove the access panel. For unit sizes 3, 6, 10 and 12,
see
Figure
47. For unit sizes 8, 14, 17, 21, 25, and 30, see
Figure
48.
Routine Maintenance
Access panel
can now be
removed